Mitsubishi Electric MXZ-3C30NA Service Manual page 96

Outdoor unit
Hide thumbs Also See for MXZ-3C30NA:
Table of Contents

Advertisement

OPERATING PROCEDURE
5. Removing the expansion valve
(1) Remove the top panel, and the service panel (Refer to 1).
(2) Disconnect the power supply and indoor/outdoor connect-
ing wire.
(Gas recovery is not required if the unit is pumped down.)
(3) Remove the LEV coils.
(4) Detach the brazed parts of expansion valves and pipes.
© Copyright 2014 MITSUBISHI ELECTRIC CORPORATION
Issued: Dec. 2016. No. OBH702 REVISED EDITION-E
Issued: Jul. 2016. No. OBH702 REVISED EDITION-D
Issued: Mar. 2016. No. OBH702 REVISED EDITION-C
Issued: Feb. 2016. No. OBH702 REVISED EDITION-B
Issued: Oct. 2014. No. OBH702 REVISED EDITION-A
Published: Sep. 2014. No. OBH702
Made in Japan
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Photo 11
Discharge pipe
brazed part
Compressor nuts
Specifications are subject to change without notice.
96
PHOTOS
Suction pipe
brazed part
Expansion
LEV coils
valves