LG Tri-Zone Multi F Installation Manual page 46

Outdoor unit, multi-zone heat pump systems 1.5 to 5 tons
Table of Contents

Advertisement

REFRIGERANT PIPING PREPARATION
Refrigerant Charge
Multi F MAX Systems
- CF (Correction Factor) x 3.53
• Number of installed length of branches depends on system specifications.
Table 36:
Outdoor Unit Model
LMU480HV
LMU540HV
LMU600HV
Figure 58: Multi F MAX Additional Refrigerant Charge Example.
LMU540HV
A
A
BD Unit
46
Main Piping Length
Chargeless Pipe Length
of Main Pipe (L) (ft.)
16.4
16.4
16.4
BD Unit
A
B1
B2
18,000
9,000
B4
9,000
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Additional Charge
Chargeless Pipe Length
Needed (a) (oz./ft.)
per Branch Pipe (B) (ft.)
0.54
0.54
0.54
• Total main pipe (A) = 60 ft.
• Each branch pipe
B1 =
B2 =
B3 =
B4 =
B5 =
Additional Charge
B3
= (60 - 16.4) x 0.54
+ (49 - 16.4) x 0.22
9,000
+ (17 - 16.4) x 0.22
+ (17 - 16.4) x 0.22
+ (10 - 16.4) x 0.22
+ (23 - 16.4) x 0.22
B5
– (8 - 5) x 3.53
18,000
= 20.43 oz.
MULTI
MULTI
Branch Piping Length
Additional Charge
Needed (b) (oz./ft.)
16.4
16.4
16.4
49 ft.
17 ft.
17 ft.
10 ft.
23 ft.
F
F
MAX
0.22
0.22
0.22