Jet MAXI D125 Operation & Maintenance Manual page 19

Digital pressurisation equipment
Table of Contents

Advertisement

The following settings are for experienced engineers only. Incorrect configuration of these
settings can cause the equipment not to function correctly, and may cause damage to the
equipment, system or property.
#
Menu Item
16 PUMPS NUMBER
17
PUMP TYPE
18
PUMP SENSE
19
SENSOR TYPE
SPC
20
CONTROLLER
21
ADDITIVE
22
ID NUMBER
RELAY
23
INVERSION
24
OVERRUN
PRESSURE
25
ALARM AUTO
RESET
26
CASCADE
27
BOOST
SOLENOID
28
CONTROLLER
Note:
21 = GLYCOL UNIT / 28 = FLOMAT ON (>7.3 VERSION CONTROLLER)
We reserve the right to change designs and technical specifications of our products
The number of pumps installed in the pressurisation unit.
This can be set to either 1 or 2.
The type of pump installed in the pressurisation unit.
There are two options, which are as follows:
0 – Centrifugal Pump (Flexfiller /Digifiller/ Midi)
1 – Piston Pump (mini units only)
Disabling this option will stop the controller from monitoring the pumps and
generating <PUMP FAIL> faults.
It is not recommended to disable this option. Please consult Flamco Technical
before doing so.
The type of pressure sensor installed in the unit.
There are two options which are as follows:
1 – 1-6V Output, 0-10 Bar Range
2 – 1-6V Output, 0-16 Bar Range
Not required on standard Pressurisation unit
Not required on standard Pressurisation unit
A user configurable identification number.
This option does not serve any functional purpose.
When enabled, all normally open fault contacts (i.e. all except the common
alarm) are converted to normally closed.
Allows the pump to continue running for a set period of time after the required
pressure has been reached.
This will prevent the pumps from 'hunting'.
The value can be set from 0 – 10 seconds.
When enabled, the <HIGH PRESSURE> and <LOW PRESSURE> alarms will be
cleared automatically if and when the pressure returns to normal.
If disabled, the alarms must be manually reset.
Allows the pumps to operate in duty/assist mode.
After either pump starts, the other pump will start after a set period of time.
This option can be set to OFF, or 5 – 30 seconds.
When enabled, the controller will allowing the pumps to run even if the system
pressure is zero.
When enabled, the "high water" input is used to trigger a top up solenoid valve
connected to the "sensor healthy" volt free contact.
This option should only be enabled on units which utilize a solenoid valve as the
means of top-up.
www.wolseley.co.uk
Function
.
Default
Value
2
1
YES
1
NO
NO
01
NO
5
YES
OFF
YES
NO
Rev 8.1 Oct-15
Page 19 / 42