④ Room Temperature control from DDC or Rotary S/W
According to Dip S/W(SW03) Setting, you can set up the Function of Room Temperature control.
Dip S/W(② SW03)
ON
No 1
OFF
ON
No 3
OFF
Setting
Dip S/W
ON
No 4
OFF
ON
No 6
OFF
• Dip S/W(SW03) NO 4 : OFF
Rotary
S/W(①) Number
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Rotary S/W
R R o o t t a a r r y y S S / / W W
RS485 Communication with Single CAC
Not available
Possible to control Room Temperature Function (Default)
Only Monitoring (DO Signal only is enable)
DDC Control (Wiring No. AI 10-4)
Rotary S/W(SW_TYPE) Control
Room Temperature Default setting (Cooling 18°C, Heating 30°C)
Room Air(or return air) temperature control using Al signal and Rotary S/W
Room Temp.(°C) Cooling
Not available
18
18
18
19
20
21
22
23
24
25
26
27
28
29
30
Dip S/W(SW03)
Function
Room Temp.(°C) Heating
Not available
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30