Table Of Contents Unit Identification ... 2 Electrical Data ... 3 Specifications ... 4 How to Operate the Air Conditioner with Remote Control ... 5 Method of Charging/Repairs ... 6 Compressor Replacement ...7 Troubleshooting ... 8-10 Wiring Diagrams for 2010 Model ... 11 Exploded View of Parts for 2010 Model ...
Unit identification COMPACT PROGRAMMABLE 3rd and 4th Digit - Approximate BTU/HR (Cooling) Heating BTU/Hr capacity listed in the Specification/Performance Data Section RAC Serial Number Identification Guide Serial Number Decade Manufactured Year Manufactured Month Manufactured A=Jan D=Apr G=Jul B=Feb E=May H=Aug C=Mar F=Jun J=Sept...
Be sure that branch circuit or general purpose outlet is grounded. Ground wire must be connected to ground screw located in lower right corner of air conditioner when air conditioner is in cabinet. (CP 14, 18, 24) Receptacle The field supplied outlet must match plug on service cord and be within reach of service cord.
Permissible Excessive Operating Pressure for the Suction Side ( P S I ) Dimension (L/W/H)( inch ) Dimension of Package (L/W/H)( inch) Net Weight /Gross Weight ( LBS ) Refrigerant Charge ( OZ ) CP15F10 CP18F30 CC05103400 CC05103410 COOLING COOLING...
1º until it reaches 64°F (18°C). To set Timer for a 1- to 24-hour delay before air conditioner is turned o (air conditioner must be On): 1. Press TIMER. Indicator light on air conditioner control panel will ash.
method of charging / repairs The acceptable method for charging the RAC system is the Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate. The weighed in method should always be used whenever a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant...
comPreSSor rePlacement recommended procedure for compressor replacement WARNING RISK OF ELECTRIC SHOCK Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service. Failure to do so could result in electric shock, serious injury or death. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing.
coolinG onlY room air conditionerS: troUBleSHootinG tiPS Fuse blown or circuit tripped Power cord not plugged in System switch in “OFF” position Unit does not run Inoperative system switch or open control board Loose or disconnected wiring at switch, control board or other com- ponents Dirty fi...
Page 11
Instruct customer of waiting period Check voltage with unit operating. Check for other appliances on circuit. Air conditioner should be in separate circuit for proper voltage & fused separately Refer to appropriate wiring diagram...
coolinG onlY room air conditionerS: troUBleSHootinG tiPS Water “spitting” into room Excessive moisture Thermistor short cycles Prolonged off cycles (automatic operation) Outside water leaks Sublimation: When unconditioned saturated, outside air mixes with conditioned air, condensation forms on the cooler surfaces Downward pitch of installation is too steep towards back of unit Restricted coil or dirty fi...