Refrigerant piping system
Branch pipe Fitting
Y branch
A
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
A
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Insulator
(included with kit)
Header
40
Outside Unit
B
Horizontal
plane
Viewed from point A
in direction of arrow
Liquid and gas
pipe joints
B
C
To Outside Unit
A
B
To Branch Piping or Indoor Unit
Within +/- 10°
Tape
(field supply)
Insulator for
field piping
A
To outside unit
B
To indoor unit
• The indoor unit having larger capacity must be
installed closer to Ⓐ than smaller one.
• If the diameter of the refrigerant piping selected
A
by the procedures described is different from
the size of the joint, the connecting section
should be cut with a pipe cutter.
ⓒ Pipe cutter
• When the number of pipes to be connected is
smaller than the number of header branches,
install a cap to the unconnected branches.
Facing
Facing
downwards
upwards
Within ± 3°
Within ± 3°