Mitsubishi Electric CITY MULTI PUHY-EP200YLM-BS Installation Manual page 41

Air-conditioners for building application inverter, outdoor unit
Table of Contents

Advertisement

(2) When MA remote controllers are connected
* Move the power jumper from
CN41 to CN40. *
1
* SW5-1: ON *
2
* Leave the power jumper
connected to CN41.
* SW5-1: ON *
2
*1 When a power supply unit is not connected to the centralized control transmission cable, move the power jumper from CN41 to CN40 on
only one of the outdoor units.
*2 If a system controller is used, set SW5-1 on all of the outdoor units to ON.
*3 When a PAR-31MAA is connected to a group, no other MA remote controllers can be connected to the same group.
Maximum allowable length of control cables
Transmission cables via outdoor units
Transmission cables
Remote controller cables
(3) When a transmission booster unit is connected
TB7
TB7
Shielded cable
*1 Daisy-chain terminals (TB3) on outdoor units together in the same refrigerant system.
*2 Leave the power jumper connected to CN41.
Maximum allowable length of control cables
Transmission cables
Remote controller cables
WT07281X03
Group 1
L
+ L
1
2
L
, L
1
3
m
+ m
1
TB7
L
+ L
1
2
L
+ L
6
5
, ℓ
≤ 10 m (32 ft)
1
2
* If the length exceeds 10 m (32 ft), the length that exceeds 10 m (32 ft) needs
to be included in the maximum allowable length of transmission cables
above.
GB-39
Group 3
Group 5
+ L
+ L
, L
+ L
+ L
≤ 500 m (1640 ft)
3
4
1
2
6
+ L
, L
, L
+ L
≤ 200 m (656 ft)
4
6
2
6
, m
+ m
+ m
+ m
≤ 200 m (656 ft)
2
1
2
3
4
Earth
+ L
+ L
+ L
, L
+ L
+ L
+ L
3
5
6
1
2
3
5
+ L
+ L
, L
+ L
+ L
+ L
≤ 200 m (656 ft)
3
4
4
3
5
7
Shielded cable
Sub remote controller
System controller
+ L
, L
+ L
+ L
,
7
1
2
4