Field Settings (Esp Setting) Duct Type Only - Friedrich FPHFC36A3B Wi-Fi Service & Parts Manual

Table of Contents

Advertisement

INSTALLATION

Field Settings (ESP Setting) Duct Type Only

The static pressure can be freely adjusted by using specific wire remote controller.
LCD
YXE-C01U(E)/YXE-C02U(E)
Static pressure setting:
1
Hold down both"MODE"button and"ADD.FUNC."button for 3 seconds, symbol
blinking at the same time.
2
Press" / "button to adjust parameter number until display "17", and press "ENTER"button to entering
system parameter adaption state, symbol
3
Select desired parameter code 10 by pressing
4
Select desired function code to rewrite the parameter values by pressing " /
"ENTER" button to confirm.
5
Press "ON/OFF"button or "CANCEL"button to quit.
73
Model
Error Indicator
(Capacity
Btu/h)
Parameter Code
9K/12K/18K
Function Code
stop blinking.
" / "
button , and press "ENTER" button to confirm.
The range of
Function code set
static pressure
0-50, more than 50 is
0-0.015 in.Hg
0.015 in.Hg (50 Pa),
(0-50Pa)
[default: 0 (0 in.Hg or 0Pa)]
and parameter code
"button , and press