Mitsubishi Electric PUHZ-W112VHA Service Manual page 38

Air to water heat pump
Hide thumbs Also See for PUHZ-W112VHA:
Table of Contents

Advertisement

SW2 setting
Pipe temperature/Liquid (TH3) when
error occurred
ON
−40 to 90
1
2 3 4 5 6
Discharge temperature (TH4) when error
occurred
3 to 217
ON
1
2 3 4 5 6
Compressor current when error occurred
0 to 50
ON
1
2 3 4 5 6
Error history (1) (latest)
Alternate display of faulty unit
ON
number and check code
1
2 3 4 5 6
Error history (2)
Alternate display of faulty unit
ON
number and check code
1
2 3 4 5 6
Compressor operation duration
0 to 999
ON
1
2 3 4 5 6
LEV-B opening when error occurred
ON
1
2 3 4 5 6
Capacity settings
ON
1
2 3 4 5 6
OCH562D
Display detail
The black square (
Explanation for display
−40 to 90
(When the coil thermistor detects 0: or below, "–"
and temperature are displayed by turns.)
(Example) When - 15:;
0.5 s
3 to 217
(When the temperature is 100: or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130:;
0.5 s
0 to 50
When no error history,
" 0 " and "– –" are displayed by turns.
When no error history,
" 0 " and "– –" are displayed by turns.
0 to 999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 s
0 to 500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 s
The outdoor capacity code is shown as below
Model
Code
PUHZ-W112
20
38
) indicates a switch position.
0.5 s
2 s
15
0.5 s
2 s
1
30
0.5 s
2 s
2
45
0.5 s
2 s
1
50
Unit
:
:
A
Code
display
Code
display
Minute
Pulse
Code
display

Advertisement

Table of Contents
loading

Table of Contents