REFRIGERANT SYSTEM DIAGRAM

PUHZ-W112VHA
PUHZ-W112VHA-BS
PUHZ-W112VHAR1
PUHZ-W112VHAR1-BS
Water OUT
Plate HEX
TH32
Water IN
TH6
Symbol
Part name
COMP
Compressor
H/P SW
High pressure switch (63H)
L/P SW
Low pressure switch (63L)
Plate HEX
Plate Heat Exchanger
REV/V
Reversing (4-way) valve (21S4)
STOP VALVE
Stop valve
CHECK/V
Check valve
P-Sensor
Pressure sensor (63HS)
P/B
Power board
LEV-A
Linear expansion valve-A
LEV-B
Linear expansion valve-B
TH33
Suction temperature thermistor
TH32
Inlet water temperature thermistor
TH3
Liquid temperature thermistor
TH4
Discharge temperature thermistor
TH6
Plate HEX liquid temperature thermistor
TH7
Ambient temperature thermistor
TH8
Heat sink temperature thermistor
TH34
Comp. surface temperature thermistor
Power Receive
Power Receiver
r
*1
: PUHZ-W112VHA(-BS), PUHZ-W112VHAR1(-BS), PUHZ-W112VHAR2(-BS)
*2
: PUHZ-W112VHAR3(-BS)
OCH562D
PUHZ-W112VHAR2
PUHZ-W112VHAR2-BS
PUHZ-W112VHAR3
PUHZ-W112VHAR3-BS
STOP VALVE
REV/V
CHECK/V
Strainer
(#100)
Power
Receiver
Strainer
(#100)
LEV-B
Strainer(#100)
DC inverter scroll compressor (Mitsubishi Electric Corporation)
For protection (OFF: 4.15MPa)
For protection (OFF: −0.03MPa)
MWA2-46LM (MITSUBISHI)
Change the refrigerant circuit (Heating/Cooling) and for Defrosting
For refrigerant charge
High pressure/Low pressure/For production test use
For calculation of the condensing temperature from high pressure
Inverter power board
Heating: Secondary LEV
Heating: Primary LEV
For LEV control
For freeze protection and for compressor frequency control
Heating: Evaporating temperature
For LEV control and for compressor protection
Heating: Sub cool liquid temperature
For fan control and for compressor frequency control
For power board protection
For compressor protection
For accumulation of refrigerant
15
P-Sensor
CHECK/V
H/P SW
L/P SW
TH4
TH33
TH34
Strainer
(#100)
COMP
Detail
*1
/ACH-70X-52H(ALFA LAVAL)
Cooling: Primary LEV
Cooling: Secondary LEV
Cooling: Sub cool liquid temperature
TH7
TH3
Distributor
Strainer(#100)
TH8
P/B
LEV-A
Refrigerant flow in cooling
Refrigerant flow in heating
*2
Cooling: Evaporating temperature