Mitsubishi Electric PUHZ-W112VHA Service Manual page 27

Air to water heat pump
Hide thumbs Also See for PUHZ-W112VHA:
Table of Contents

Advertisement

Check method of DC fan motor (fan motor/outdoor multi controller circuit board)
1 Notes
· High voltage is applied to the connector (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It may damage the outdoor controller circuit board and fan motor.)
2 Self check
Symptom: The outdoor fan cannot rotate.
Fuse check
Check the fuse (F5) on outdoor
controller circuit board.
Yes
Is the fuse normal?
No
Wiring contact check
Contact of fan motor connector
(CNF1,2)
Is there contact failure?
No
Power supply check
Measure the voltage on the outdoor controller circuit board.
TEST POINT 1: V
280–380 V DC (between 1 (+) and 4 (−) of CNF1,2)
DC
TEST POINT 2: V
15 V DC
CC
Is the voltage normal?
No
Replace the outdoor
controller circuit board.
Check fan motor rotation.
Fail
Replace the defective fan motor.
OCH562D
Disconnect the FAN motor connector
and measure the resistance of
connector pins. Refer to "8-4. HOW
TO CHECK THE PARTS".
Yes
Correct the wiring.
(between 5 (+) and 4 (−) of CNF1,2)
Yes
Replace the defective fan motor.
Check fan motor rotation.
Replace the outdoor
controller circuit board.
OK
Complete.
Is the fan motor normal?
No
Replace the outdoor controller
circuit board (C.B) and the
defective fan motor.
Yes
OK
Fail
27
Yes
Replace the outdoor controller
circuit board (C.B).
Complete.