11-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on>
Abnormal points and detection method
Error Code
None
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power sup-
ply.
63H: High-pressure switch
F5
(5201)
1 No voltage is supplied to termi-
nal block (TB1) of outdoor unit.
a) Power supply breaker is
b) Contact failure or disconnec-
c) Open phase (L, L2 or N
2 Electric power is not supplied
to power supply terminal of out-
door power circuit board.
a) Contact failure of power
b) Open phase on the outdoor
3 Electric power is not supplied
to outdoor controller circuit
board.
a) Disconnection of connector
4 Disconnection of reactor (DCL
or ACL)
5 Disconnection of outdoor noise
filter circuit board or parts fail-
ure in outdoor noise filter circuit
board (RP200/250)
6 Defective outdoor power circuit
board
7 Open of rush current protect
resistor (RS) (RP100-250Y)
8 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller
circuit board
(Note 1) Refer to indoor unit section for code P and code E.
Case
turned off.
tion of power supply terminal
phase)
supply terminal
power circuit board
(Disconnection of terminal
on outdoor power circuit
board)
(CNDC)
42
Judgment and action
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block. (TB1)
c) Connection of power supply terminal
block. (TB1)
2 Check following items.
a) Connection of power supply terminal block.
(TB1)
b) Connection of terminal on outdoor power
circuit board.
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector, LD1
and LD2 for RP35-71V and CNDC for
RP100-250, on the outdoor power circuit
board (V) / noise filter (Y). Refer to 11-9.
4 Check connection of reactor. (DCL or ACL)
RP35-71V: Check connection of "LO" and
"NO" on the outdoor noise filter circuit board.
Check connection of "R" and "S" on the
outdoor power circuit board.
Refer to 11-9.
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 11-9.
6 Replace outdoor power circuit board.
7 Replace rush current protect resistor (RS)
* Power circuit board might be short-circuit.
Check the power circuit board. (Refer to
11-9.)
8 Replace controller board (When items
above are checked but the units can not be
repaired.)
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.