11.2. CS-E15GKEW CU-E15GKE
CS-E15GKE-3 CU-E15GKE-3
11.2.1. Select The Best Location
INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Rated
Piping size
Length
Model
(m)
Gas Liquid
E15GK
1/2"
1/4"
7.5
Example: For E15GK
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 50g ...... (10 - 7.5) m x 20 g/m = 50 g
Max
Min.
Max.
Additional
Elevation
Piping
Piping
Refrigerant
(m)
Length
Length
(m)
(m)
15
3
15
11.2.2. Indoor/Outdoor
Diagram
(g/m)
20
36
Unit
Installation