Installation Manual
5.0 COMMISSIONING
The filters fitted inside the unit are protected with a plastic film.
Prior to commissioning remove the covers (Figure 20, take off the
film and replace.
•For the required air flow rates please refer to the design
specification for the property, follow Scetion 3.7, or refer to
building regulations ADF 2010.
•The unit is supplied with independent control for both normal and
boost airflows (Figure 18).
•Correct commissioning is essential to ensure the ventilation air
flow rates are met. It also ensures the unit is not over ventilating
and causing excessive power consumption.
•Commissioning should be carried out in accordance with building
regulations document "Domestic ventilation compliance guide".
www.planningportal.gov.uk/building regulations/approved
documents/partf/associated
A calibrated moving vane anemometer and hood will be required
to carry out commissioning.
•Adjustment valves should be locked in place to prevent further
adjustment.
•Once commissioned the home owner / tenant should be informed
that the unit should not be adjusted as it will have a detrimental
effect on the indoor air quality and could result in condensation
and mould growth. The clear panel covering the control has
an adhesive panel which should be exposed and sealed post
commissioning to prevent tampering.
•Speed 1 is limited to never exceed speed 2, when commissioning
speed 2 should always be set first.
18
Front Panel Unit Control Detail
Post commissioning remove
Ventilation Controls
adhesive backing and seal
Speed 1
Speed 2
Speed 3
+
-
+
-
+
- +
- +
- +
-
Supply Extract Supply Extract Supply Extract
Power
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
Humidity adjustment situated
behind front panel, panel must
be removed for access.
Fan
This should only be carried
Failure
out by a qualified person.
MRXBOXAB-ECO2B-AE(H)SW
6.0 CONTROLS
6.1 Humidity Adjustment
This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the
humidity exceeds the set point the unit will boost to that set by the
commissioned boost speed. The set point can be found behind the front
of the unit (Figure 18) and is at its least sensitive when turned fully
clockwise. Note that the sensor is measuring humidity from all the wet
rooms at the same time and should not be relied on to solely boost
the unit. Additional switch should be used local to the wet rooms (see
wiring diagrams).
Adjustment only to be carried out by qualified person, isolate
power before removing cover.
6.2 Status Indication
The status of the unit is indicated by a series of LED's on the front cover.
The variants are listed below.
The display on the unit control panel will not indicate when a
higher speed setting has been triggered by an external source.
19
LED Indicators
Speed 1
Speed 2
Speed 3
Supply Fan Fault
Extract Fan Fault
Frost Protection
Filter Change
HX Bypass
(AB units only)
6.3 Integral Automatic HX Bypass
Intake and extract temperatures are monitored at the point the
airflows enter the unit, if the range falls within the set parameters the
bypass damper is opened automatically to target an indoor comfort
temperature all year round.
The extract temperature is an average from all wet rooms. If this
exceeds 25°C the unit may go into bypass depending on outside
temperatures.
6.4 Summer / Winter Switch
When the switch position is set to Summer the integral automatic
summer bypass is fully operational, in the alternative Winter position
the HX bypass is disabled to ensure the unit is constantly in heat
recovery mode.
6.5 Speed 3 Operation (SW Units Only)
Speed 3 will be non-operational if the intake temperature is greater
than the extract temperature.
6.6 Frost Protection
In the event of the intake air temperature at the unit dropping below
the predetermined set point (-5°C as standard) the supply fan will
reduce to minimum speed, once the temperature rises above the set
point the fan will return to its commissioned speed.
Please note this mode will only activate after ten days of continuous
run time. If commissioning of the unit is outside of this time frame
17. 11. 21. Document Number 672002
8