NuAire MRXBOXAB-ECO-LP2B-SW Installation Manual
NuAire MRXBOXAB-ECO-LP2B-SW Installation Manual

NuAire MRXBOXAB-ECO-LP2B-SW Installation Manual

Mechanical ventilation unit with heat recovery for ceiling void mounting - standard hand unit & opposite hand unit

Advertisement

MRXBOXAB-ECO-LP2B-SW (Standard Hand Unit)
MRXBOXAB-ECO-LP2BHSW (Opposite Hand Unit)
Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting
Installation Manual
1.0 SAFETY INFORMATION
The provision of the electrical supply and the connection of the unit to the electrical supply
must be carried out by a qualified electrician in accordance with latest edition of the wiring
regulations.
Isolate from power supply before removing any covers. During installation / maintenance ensure
all covers are fitted before switching on the mains supply.
All-pole disconnection from the mains as shown in the wiring diagram must be incorporated
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with
latest edition of the wiring regulations.
This unit must be earthed.
Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct
runs terminating close to the fan must be adequately protected by suitable guards.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard. The replacement cord must be of the same
technical specification as the original cord or greater.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of
gas or other fuel-burning appliances.
This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
1.1 Hazard Symbols
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing,
operating or maintaining this product.
1.2 Important Information
This manual contains important information on the safe and
appropriate assembly, transport, commissioning, operation,
maintenance, disassembly and simple troubleshooting of the product.
While the product has been manufactured according to the accepted
rules of current technology, there is still a danger of personal injury or
damage to equipment if the following general safety instructions and
the warnings contained in these instructions are not complied with.
•Read these instructions completely and thoroughly before
working with the product.
•Keep these instructions in a location where they are accessible
to all users at all times.
•Always include the operating instructions when you pass the
product on to third parties.
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
1.3 Personal Protective Equipment
The following minimum Personal Protective Equipment (PPE) is
recommended when interacting with Nuaire product:
•Protective Steel Toed Shoes - when handling heavy objects.
•Full Finger Gloves (Marigold PU800 or equivalent) - when
handling sheet metal components.
•Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent)
- when conducting light work on the unit requiring tactile
dexterity.
•Safety Glasses - when conducting any cleaning/cutting operation
or exchanging filters.
•Reusable Half Mask Respirators - when replacing filters which
have been in contact with normal room or environmental air.
Nuaire would always recommend a site specific risk assessment by a
competent person to determine if any additional PPE is required.
05. 11. 21. Document Number 672000
EMC Directive
2014/30/EU
LVD Directive
2014/35/EU
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MRXBOXAB-ECO-LP2B-SW and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NuAire MRXBOXAB-ECO-LP2B-SW

  • Page 1 Nuaire would always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 2: Mechanical Installation

    (Figures 5 & 6). maintenance such as filter change. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 3 This should be used as the default value. If a greater level of occupancy is expected add 4 l/s per occupant. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 4 Access Requirements Bypass Bypass Heat Drip tray damper chamber exchanger View from control side End view 735 (Filter access distance) Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 5 Spigot 3. Intake Extract 885 hole centres Supply Extract 21.5mm condensate pipe View from control side End view 735 (Filter access distance) Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 6: Electrical Installation

    Light have a minimum contact 3 Pole Grey Light Isolator separation of 3mm. Switch Optional 3 Speed Switch (Double Pole) Kitchen Switch Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 7 This mode will only activate after ten days of continuous run time. If commissioning of the unit is outside of this time frame please notify the after sales department prior to site visit. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 05. 11. 21. Document Number 672000...
  • Page 8: Maintenance

    The filter can now be extracted by pulling the removal loop on the front edge of the filter. Once the filters have been inspected return Ensure that Nuaire product is made safe from any electrical / water or replace them as necessary.