MRXBOXAB-ECO4-1Z (Standard Unit)
MRXBOXAB-ECO4-1Z-OH (Opposite hand Unit)
Mechanical Ventilation Units with Heat Recovery
Installation and Maintenance
1.0 INTRODUCTION
The ECO4-1Z range of units are designed to offer improved sound
levels and an aesthetically pleasing installation by housing a
Mechanical Ventilation with Heat Recovery (MVHR) unit and
attenuator inside an acoustically lined enclosure.
The MVHR unit is fitted with two independent fans to provide
mechanical supply and extract ventilation, each fan has full speed
control for background and boost ventilation rates. To recover heat
from the extract air, the heat exchanger block is utilised. The heat
exchanger can recover up to 95% of the normally wasted heat.
The units also incorporate an integral humidistat and frost protection,
see sections 7.1 & 9.1 for details.
The unit is not supplied with any mounting brackets; a suitable
mounting structure with means of securing the unit in place is
required.
2.0 INSTALLATION
Installation must be carried out by competent personnel in accordance
with the appropriate authority and conforming to all statutory
governing regulations. All mains wiring must be in accordance with the
current I.E.E. Regulations, or the appropriate standards. Ensure that the
mains supply (Voltage, Frequency and Phase) complies with the rating
label.
Please note a clear working space is required around the installed unit
to allow the cover to be removed and provide sufficient access for
maintenance such as filter change. A minimum of 480mm is required in
front of the unit.
The fan must be installed indoors, on a suitable structure away from
direct sources of frost, heat and water spray or moisture generation. For
a vibration-free result the unit must be mounted to a solid structure.
Figure 3. Mounting point locations.
4x M10 Flanged head bolts
protruding from base to be
accomodated in structure design.
(standard hand configuration).
For opposite hand configuration position
will be mirrored to the other side.
Summer / Winter Cable entry point.
nuaire.co.uk
029 2085 8400
726
=
43
143
48
Figure 1. Airflow through unit (Standard unit).
Exhaust air
from house
to outside
Figure 2. Airflow through OH unit (Opposite hand unit).
Supply air
to house
=
43
2x Rivet Heads
48
Mains Cable Connection
28. 07. 20. Leaflet Number 671838
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
Intake air
from outside
Supply air
to house
Extract air
from house
Extract air
from house
Exhaust air
from house
to outside
Intake air
from outside
2x Hatched regions details
compulsory support areas,
further support may be required
depending on structure design
(supplied by others).
4x M8 Mounting Points
Note:
Any Items being accomodated in structure design should
include sufficient clearance to allow for assembly tolerances
and for ease of installation when positioning on site.
1
Need help?
Do you have a question about the MRXBOXAB-ECO4-1Z and is the answer not in the manual?
Questions and answers