Configuration; Field Setting - Daikin FCAHG100HVEB Manual

Table of Contents

Advertisement

7 Configuration

▪ 2 user interface control. (2 remote controllers control 1 indoor
unit)
1~ 50 Hz
220-240 V
c
d
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e1
Main user interface
e2
Optional user interface
c
b
d
c
a
Service cover (with wiring diagram on the back)
b
Opening for cables
c
Connection of interconnection cable (including earth)
d
Cable tie
e
Connection of user interface cable
7
Configuration
7.1

Field setting

Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
▪ Ceiling height
▪ Design decoration panel (if applicable)
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• C1: First code number
• C2: Second code number
: Default
(2)
Fan speed:
• LL: Low fan speed
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by Low fan speed (1) or by Setup
volume (2).
Installer and user reference guide
18
b
a
e2
e1
d
10~15
7
e
70~90
e
b
a
(mm)
▪ Air flow direction
▪ Air volume when thermostat control is OFF
▪ Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor,
capacity class and air flow directions.
▪ For 3-way and 4-way air flows (which require an optional blocking
pad kit), see the installation manual of the optional blocking pad
kit.
▪ For all-round air flow, use the table below.
If the distance to the floor is (m)
FCAHG71
FCAHG100~140
≤2.7
2.7<x≤3.0
3.2<x≤3.6
3.0<x≤3.5
3.6<x≤4.2
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS
check if the correct values are set.
If the ... decoration panel is used
Standard or self-cleaning
Design
Setting: Air flow direction
This setting must correspond with the actual used air flow directions.
See the installation manual of the optional blocking pad kit and the
manual of the user interface.
Default: 01 (= all-round air flow)
Example:
a
b
3
3
2
4
2
4
1
1
a
All-round air flow
b
4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)
c
3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1 If you have set the fan to operate, set the air volume speed:
If you want
Outdoor unit
General
(2)
During cooling
LL
operation
Setup volume
(1)
Then
M
C1
C2
≤3.2
13 (23)
0
01
02
03
(1)
Then
M
C1
C2
13
15
01
(23)
02
c
3
2
1
(1)
Then
M
C1
C2
3MXM, 4MXM,
5MXM
12
6
01
(22)
(2)
02
FCAHG71~140HVEB
Split system air conditioners
4P561449-1A – 2019.09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcahg71hvebFcahg125hvebFcahg140hveb

Table of Contents