Appendix B: Sensiscan 2000; Mounting In Cab-A3F Or Cab-B3F Cabinet - Fire-Lite Alarms APS-6RF Instruction Manual

Auxiliary power supply
Hide thumbs Also See for APS-6RF:
Table of Contents

Advertisement

Mounting in CAB-A3F or CAB-B3F Cabinet

This section contains instructions for the installation of the Auxiliary
Power Supply onto a CHS-4F chassis used in a CAB-A3F or CAB-B3F
cabinet.
To mount the APS-6RF, follow these instructions:
Step
1
2
3
4
5
6
APS-6RF Instruction PN 50893:B 7/20/00

Appendix B: Sensiscan 2000

Action
Remove plastic cover from APS-6RF.
If 240 VAC is to be used, cut JP1 jumper at this time. See "Configuring the
APS-6RF" on page 15.
Place the APS-6RF onto the mounting studs of the chassis.
Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the mounting studs on the chassis.
Tighten the standoffs until the APS-6RF is securely fastened to the chassis.
Reinstall the plastic chassis cover.
CHS-4F Chassis
Figure 11 Mounting an APS-6RF to a CHS-4F Chassis
Standoff
(2 places)
APS-6RF
Assembly