2. Installation

Wiring the APS-6RF

This section contains instructions for wiring the Auxiliary Power Supply
as follows:
• Typical field wiring from an APS-6RF to a control panel.
• Wiring multiple APS-6RF power supplies.
• Connecting an APS-6RF to an IC module

Field Wiring an APS-6RF

You can use J1 and J2 in place of TB2 when the APS-6RF is powering
internal modules (such as an IC-4F, ICE-4F, TC-2F, TC-4F) with
compatible connectors.
Primary and Secondary Power Connections - See appendix for your
specific system information.
Caution: When finished wiring AC connections, install the press-fit
!
terminal block cover over TB1 AC connections.
J9
JP2
12
Output Circuit 3: Not Applicable
Output Circuit 2 (24 VDC)
Output Circuit 1 (24 VDC)
– + – + – +
J1
J2
+
+
TB2
J3
Trouble Bus In/Out
BATT (+)
BATT (–)
HOT
JP3
NEUTRAL
EARTH
Figure 4 Typical Wiring for an APS-6RF
Output Circuit 1: Power-limited
3 A @24 VDC (+10, –15%)
Output Circuit 2: Power-limited
3 A @24 VDC (+10, –15%)
Secondary Power
24 VDC batteries.
Primary Power
120 VAC or 240 VAC.
Earth Ground - Connects to
chassis or
EARTH
main power supply. If two or more
units are connected, secondary
units connect to earth ground on the
previous APS-6RF in the chain.