Venting - Rheem EcoSense ECOH200DV Series Use And Care Manual

94% condensing tankless water heater
Hide thumbs Also See for EcoSense ECOH200DV Series:
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Venting for Direct-Vent Water Heater
DANGER:
the water heater to the outdoors as outlined in
this Venting section will result in death or serious
personal injury. To avoid the risk of fire, explosion,
or asphyxiation from carbon monoxide, NEVER
operate the water heater unless it is properly
vented and has adequate air supply for proper
operation as outlined in this Venting section.
WARNING:
Refer to page 29 for required clearances to
combustible materials. Improper clearances can
cause explosion or fire resulting in death, personal
injury, and/or product damage.
CAUTIONS:
• Check to make sure flue gases do not recirculate
into the air intake terminal when using direct
venting. If the water heater is having service issues,
flue recirculation may be a contributing factor.
• Even when the minimum vent terminal separation
distances are followed, recirculation may still
occur depending upon the location outside
the building, the distance from other buildings,
proximity to corners, weather conditions, wind
patterns, and snow depth.
• Periodically check to make sure that flue
recirculation is not occurring. Signs of flue gas
recirculation include frosted or frozen intake
terminals and condensate in the intake terminal
and venting system.
• Correction to flue recirculation may involve
angling the intake away from the exhaust
terminal and increasing the distance between
them. Check to be sure the intake and exhaust
terminals are not obstructed, especially during
periods of below-freezing weather.
Venting Requirements
The installation of venting must comply with
national codes, local codes, and the vent
manufacturer's instructions.
The vent exhaust and air intake must be vented
outside as described in these instructions. DO NOT
vent this water heater through a chimney. It must be
vented separately from all other appliances.
NOTICE:
only the following recommended pipe material.
Use only 2- or 3-inch diameter pipe. Refer to local
codes for restrictions on the use of PVC, CPVC, or
ABS pipe and fittings. All exhaust venting materials
for product installed in Canada must meet ULC-S636.
Acceptable materials or equivalent:
PVC (Schedule 40, ASTM D-1785)
CPVC (Schedule 40, ASTM F-441)
34
Failure to properly vent
The unit can be vented using
ABS (Schedule 40, ASTM D-2661) (Not permitted
in Canada)
The fittings, other than the VENT TERMINAL,
should be equivalent to the following:
PVC (Schedule 40 DWV, ASTM D-2665)
CPVC (Schedule 40 DWV, ASTM F-438)
ABS (Schedule 40 DWV, ASTM D-2661) (Not
permitted in Canada)
Polypropylene
Category III Stainless Steel
DO NOT USE Schedule 20, Cell Core, Drain Pipe,
Galvanized, Aluminum, or B-Vent.
Recommended Vent Lengths
Before starting the vent installation, careful
planning should be given to the routing and
termination of the vent pipes. The length of the
vent pipes (inlet and outlet) should be kept to a
minimum. Also, see pages 37–38 and 44 for vent
terminal placement. Refer to the maximum and
minimum vent length charts for the pipe sizes that
can be used and the total equivalent length of pipe
that can be used. Do not exceed equivalent length
of pipe in maximum vent length chart.
Maximum Vent Length (intake/outlet):
Number
Maximum
of 90°
Length of 2"
Elbows
Straight Pipe
0 or 1
5.0 ft. (1.5 m)
2
3.5 ft. (1.0 m)
3
2.0 ft. (0.6 m)
4
Not available
5
Not available
6
Not available
The system will not operate if there is excessive
restriction (pressure drop) in the venting system.
Use the chart above to calculate the maximum
pipe run length with the required number of
elbows (e.g., a maximum 38 ft. [12 m] of 3" vent
pipe may be used provided there is only one 90°
elbow in the system).
A 90° elbow is equivalent to 1 ft. 6 in. (0.5 m) of
straight pipe.
The vent termination does not count as part of the
straight pipe equivalent when determining the total
vent length.
Minimum Vent Length:
Number
Minimum
of 90°
Length of 2"
Elbows
Straight Pipe
1
1.0 ft. (0.3 m)
Maximum
Length of 3"
Straight Pipe
38.0 ft. (11.6 m)
36.5 ft. (11.1 m)
35.0 ft. (10.6 m)
33.5 ft. (10.2 m)
32.0 ft. (9.8 m)
30.5 ft. (9.3 m)
Minimum
Length of 3"
Straight Pipe
1.0 ft. (0.3 m)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents