Hazardous Area; Ordering Information; Terminal Block Connections - G.M. International D1014S Instruction & Safety Manual

Sil 2 repeater power supply hart compatible din-rail
Table of Contents

Advertisement

Model:
D1014
1 channel
2 channels
Power Bus enclosure

HAZARDOUS AREA

9
Not used
10
+ Input Ch 2 for 2 wire Transmitters
11
- Input Ch 2 for 2 wire Transmitters
12
Not used
13
Not used
14
+ Input Ch 1 for 2 wire Transmitters
15
- Input Ch 1 for 2 wire Transmitters
16
Not used
G.M. International ISM0052-16

Ordering information

S
D
/B
Front Panel and Features

SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 9 / 10 years (≤10% / >10 % of total SIF).

PFDavg (1 year) 1.05 E-04, SFF 87.01%.

SIL 3 Systematic capability.

2 fully independent channels.

Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.

4-20 mA Input, Output Signal.

Hart compatible.

Input and Output short circuit proof.

High Accuracy.

Three port isolation, Input/Output/Supply.

EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1

In-field programmability by DIP Switch.

ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.

TÜV Functional Safety Certification.

Type Approval Certificate DNV and KR for maritime applications.

High Reliability, SMD components.

High Density, two channels per unit.

Simplified installation using standard DIN Rail and plug-in terminal blocks.

250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.

Terminal block connections

1
2
3
4
5
6
7
8
D1014 - SIL 2 Repeater Power Supply Hart compatible
Power Bus and DIN-Rail accessories:
DIN rail anchor MCHP065
Terminal block male MOR017
SAFE AREA
+ Output Ch 1 for Current Source mode or + Output Ch 1 for
Voltage Source mode or + Output Ch 1 for Current Sink mode
- Output Ch 1 for Current Source mode or - Output Ch 1 for
Voltage Source mode or - Output Ch 1 for Current Sink mode
+ Ch 1 Power Supply 12-24 Vdc
- Ch 1 Power Supply 12-24 Vdc
+ Output Ch 2 for Current Source mode or + Output Ch 2 for
Voltage Source mode or + Output Ch 2 for Current Sink mode
- Output Ch 2 for Current Source mode or - Output Ch 2 for
Voltage Source mode or - Output Ch 2 for Current Sink mode
+ Ch 2 Power Supply 12-24 Vdc
- Ch 2 Power Supply 12-24 Vdc
DIN rail stopper MOR016
Terminal block female MOR022
3

Advertisement

Table of Contents
loading

Table of Contents