■ FUNCTIONAL BLOCK: fbYS[0,1]
nv 60,
nv 61
• Network Variables
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_lev_percent}
nviYSVal
{-15.000...115.000}
{0.0}
• Configuration Properties
CONFIGURATION
NETWORK
PROPERTY
VARIABLE
SCPTsetpoint[0]
nviYSVal
SCPTsetpoint[1]
nviYSVal
SCPToffset
nviYSVal
SCPTgain
nviYSVal
fbYS [0,1] (Object ID : 25, 26)
Network Variables
nviYSVal
SNVT_lev_percent
Configuration Properties
nviYSVal :
SCPTsetpoint [ ]
0% and 100% setpoints
SCPToffset
Zero adjustment
SCPTgain
Span adjustment
DC current output
EXPLANATIONS
% input proportional to the current at Output 0 and 1.
TYPE
{ Range }
{ Default }
{SNVT_lev_percent}
{-15.000...115.000}
{0.0}
{SNVT_lev_percent}
{-15.000...115.000}
{100.0}
{SNVT_lev_percent}
{-15.000...115.000}
{0.0}
{SNVT_muldiv
(mulplier,divisor)}
{0...32000,10000}
{10000,10000}
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Output 0, Output 1
EXPLANATIONS
nviYSVal lower range current in % of the output range.
SCPTsetpoint[0] < SCPTsetpoint[1]
nviYSVal upper range current in % of the output range.
SCPTsetpoint[0] < SCPTsetpoint[1]
nviYSVal zero (offset) adjustment.
Added to the calculation result with SCPTsetpoint[0,1] and
SCPTgain.
nviYSVal span (gain) adjustment.
Gain = Multiplier / 10000 (Divisor is fixed at 10000.)
Applied to SCPTsetpoint[0,1].
R7L-YS2