Lochinvar EnergyRite ER202 Installation & Operation Manual page 16

Hide thumbs Also See for EnergyRite ER202:
Table of Contents

Advertisement

2
General venting
An Outdoor Installation, DirectAire Vent or
⚠WARNING
an E-Rite Vent into dead air spaces such as
alleys, atriums, and inside corners can cause
recirculation of flue gases. Recirculation of
flue gases will cause incomplete combustion,
sooting, premature failure of the jacket, vent
and heat exchanger as well as icing of the
combustion air intake during operation in
severe cold weather. Minimum clearances
between the combustion air intake and
exhaust vent terminal are specified in
the installation instructions. To prevent
recirculation of the flue gases, maintain
as much distance as possible between the
combustion air intake and the exhaust vent
terminal.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
Installation of optional vent kits
Figure 2-10_Removal of Outdoor Vent Cap
FLUE TRANSITION
ASSEMBLY
Figure 2-11_Installation of Flue Adapter and Air Inlet Collar
16
Figure 2-12_Installation of Flue Adapter and Air Inlet
Cover
Whenever a vent option other than outdoor installation is
desired, the outdoor vent cap assembly must be removed and an
optional vent kit must be installed on the pool heater. The vent
kit allows connection of the flue and/or a combustion air pipe.
The vent kit includes the flue adapter*, assembly instructions
and an air inlet collar to allow connection of an air inlet pipe
or an air inlet cover when combustion air is drawn from the
equipment room. Remove the screws surrounding the outdoor
vent cap and the four screws in the divider between the flue
outlet and air inlet chambers on the vent cap.
*A flue adapter is not provided in the E-Rite Vent Kit.
IMG00217
INLET AIR
COLLAR
Installation & Operation Manual
FLUE TRANSITION
ASSEMBLY
AIR INLET
COVER
IMG00217