Summary of Contents for Moxa Technologies MDR Series
Page 1
MDR Series Quick Installation Guide Edition 1.1, July 2016 Technical Support Contact Information www.moxa.com/support Moxa Americas: Moxa China (Shanghai office): Toll-free: 1-888-669-2872 Toll-free: 800-820-5036 Tel: 1-714-528-6777 Tel: +86-21-5258-9955 Fax: 1-714-528-6778 Fax: +86-21-5258-5505 Moxa Europe: Moxa Asia-Pacific: Tel: +49-89-3 70 03 99-0...
Page 2
Dimensions DC OK Relay Contact Contact Closed When the output voltage reaches the adjusted output voltage. Contact Open When the output voltage drop below 90% of the output voltage. Contact Ratings 30 V / 1 A resistive load. (max.) Mounting Instructions Mounting: Mount only as shown in figure, with input terminals facing downwards to allow sufficient cooling.
Page 3
Installation 1. To prevent the unit from overheating, always allow sufficient clearance around the unit for proper ventilation: 5 mm left and right, 40 mm above, and 20 mm below. You should also keep a 10 to 15 cm clearance from adjacent devices that act as a heat source. 2.
Page 4
6. Humidity warning: Do not install the unit in locations with high humidity, or near water. 7. The maximum operating temperature for the MDR series is 70°C. Derating Curve 8. The FG ( ) must be connected to PE (Protective Earth).