Technical specifications

Notice! Failure to follow specifications and local regulations may cause equipment damage. Misapplication will void
warranty.
Power Supply
Power Requirements
Power Consumption
Electrical Connection
Clock backup
Signal inputs
Temperature Inputs
Range
Accuracy
Signal outputs
Digital Switching Outputs
Switching Type
AC Switching power
Insulation strength
between relays contacts and system electronics:
between neighboring relays contacts
Environment

Operation

Climatic Conditions
Temperature
Humidity
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
Standards
Product standards
Automatic electrical controls for household and similar use
Special requirement on temperature dependent controls
Electromagnetic compatibility for
domestic sector
Degree of Protection
Pollution Class
Safety Class
Overvoltage Category
General
Dimensions (H x W x D)
Material:
Weight (including package)

Dimensions, mm (inch)

73 (2.9)
Doc: 70-00-0294, V3.1, Date: 20140508
Subject to alteration
conformity
EMC Directive
Low Voltage Directive
Front part:
Power case:
Cover, back part
Mounting Plate
32 (1.3)
© Vector Controls GmbH, Switzerland
210 – 250 V AC 50/60 Hz
Max 1W, 1.5VA
Terminal Connectors
Min 48h if charged for 24h
RT Internal, External (Sxx-Tn10 sensor)
0...50 °C (32...122 °F)
0.5°C (1°F)
Y1 to Y2
Relays
0...250V AC 1.25A max. each output
3750V AC to EN 60 730-1
1250V AC to EN 60 730-1
To IEC 721-3-3
class 3 K5
0...50 °C (32...122 °F)
<95 % r.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25...70 °C (-13...158 °F)
<95 % r.H. non-condensing
class 2M2
2004/108/EC
2006/95/EC
EN 60 730 –1
EN 60 730 – 2 - 9
Emissions: EN 60 730-1
Immunity: EN 60 730-1
IP30 to EN 60 529
II (EN 60 730-1)
II (IEC 60536)
III (EN 60 730-1)
16 x 73 x 113mm (0,7 x 2.9 x 4.5 in.)
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.)
ABS plastic (UL94 class V-0)
Galvanized Steel
Standard:
Deluxe (-D):
16 (0.7)
Space required in flush mounting box:
(H x W x D)
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.)
Distance for mounting screws:
Horizontal 55 to 60mm (2.2 to 2.4 in.)
Vertical: 55 to 93mm (2.2 to 3.7 in.)
TLC3-BCR-U Thermostat
O
PERATION
295g (10.4oz)
305g (10.7oz)
Page 2