User and display parameters (password 009)
Parameter
Description
UP 00
Enable change of operation modes,
UP 01
Enable change of set points
UP 02
Parameter not used
UP 03
Enable manual Heat/Cool change
UP 04
Enable Access to time programs
UP 05
State after power failure: 0 = OFF, 1 = ON, 2 = Last State
UP 06
Enable Economy (unoccupied) Mode.
Shift the setpoint to a lower temperature in winter or higher
temperature in summer in order to save energy. May be activated
through the POWER button, or with the external input (typically for
key card switches in hotel rooms or motion detectors for meeting
rooms.)
UP 07
Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit
UP 08
Calibrate internal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this
feature for field adjustment only as required.)
UP 09
Enable Frost Protection.
Switches to heating mode and activates the output when the control
temperature drops below 5°C or 41°F. The controller returns to
normal operation when the temperature increases above 10°C or
50°F.
UP 10
Select contents of Large LCD display in standard mode:
00 = OFF
01 = Setpoint
02 = Temperature Sensor
03 = Output Mode
UP 11
Select contents of small LCD display in standard mode
00 = OFF
01 = Setpoint
02 = Temperature Sensor
03 = Output Mode
UP 12
Clock display type: Only available for deluxe version
OFF = Show 24hour clock
ON = Show 12hour clock (AM, PM)
UP 13
Reset timer for override mode: Only available for deluxe version
0
= Reset of override mode is not active.
1...255
= delay in minutes to switch off device if ON/Economy mode
is activated while the unit is scheduled to be in OFF mode
Doc: 70-00-0294, V3.1, Date: 20140508
Subject to alteration
04 = Clock
05 = Alternative Sensor
06 = Changeover Sensor (X2)
04 = Clock
05 = Alternative Sensor
06 = Changeover Sensor (X2)
© Vector Controls GmbH, Switzerland
TLC3-BCR-U Thermostat
U
C
SER
ONFIGURATION
Range
Default
ON, OFF
ON (Enabled)
ON, OFF
ON (Enabled)
ON, OFF
ON
ON, OFF
W00 = ON
W01 = OFF
ON, OFF
ON (Enabled)
0, 1, 2
2
ON, OFF
ON
(Economy )
ON, OFF
OFF (Celsius)
-10...10
0
ON, OFF
W00 = ON
W01 = OFF
0...6
02
Temperature
0...6
Standard:
01 Setpoint
Deluxe:
04 Clock
ON, OFF
OFF (24h)
0...255
60 (Min)