Outdoor Unit
GRV97L5
Controller PCB
Part No.
Control circuit fuse
Compressor
Type
Compressor model
Nominal output
Compressor oil ... Amount
Coil resistance (Ambient temp. 25°C)
Safety devices
Type
Overload relay
Operating temp.
Operating amp.(Ambient temp. 25°C)
Run capacitor
Crank case heater
Fan & Fan Motor
Type
Q'ty ... Dia.
Fan motor model ... Q'ty
No. of poles ... rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 20°C)
Safety devices
Type
Operating temp.
Run capacitor
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
W
cc
Open
°C
Close
°C
Trip in 6 to 16 sec. at 16A
µF
VAC
W
Open
°C
Close
°C
µF
VAC
mm
m
2
9
POW-CL128E
250 V 3.15 A
Rotary (Hermetic)
C-RN80H5B 80228235
800
FV68S ... 500
C–R : 3.38
C–S : 7.49
External(OLR A)
MRA99109-9201
150±5
69±11
22.5
400
Propeller
1 ... ø400
UE6T-21D5PA-S ... 1
6 ... 650
20
BRN-WHT : 381.2
WHT-VLT : 268.1
VLT-YEL : 49.71
YEL-PNK : 84.6
Internal fuse
165±3
1.5
440
Aluminum plate fin / Copper tube
1
1.3
0.377
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
External(OLR T)
CS-7C115
115±3
95±5

Advertisement