Rheem RP13 Installation Instructions Manual page 44

R-410a outdoor units
Table of Contents

Advertisement

DIAGNOSTICS
Service Analyzer Charts
CONTAMINATION
SYMPTOM
Moisture
High head pressure
Unusual head and
suction readings
Foreign matter –
copper filings
Copper oxide
Welding scale
Soldering flux
Excess soft solder
LOSS OF LUBRICATION
SYMPTOM
Compressor failures
Low suction pressure
Cold, noisy
compressor –
Slugging
Noisy compressor
Cold, sweating
compressor
Low load
Short cycling of
compressor
SLUGGING
SYMPTOM
On start-up
TEV hunting when
running
44
POSSIBLE CAUSE
Poor evacuation on installation or during service
Noncondensibles air
Wrong refrigerant or mixed refrigerants
Copper tubing cuttings
Dirty copper piping or nitrogen not used when
brazing
Nitrogen not used during brazing
Adding flux before seating copper partway
Wrong solder material
POSSIBLE CAUSE
Line tubing too large
Low charge
Refrigerant leaks
Dilution of oil with refrigerant
Migration
Flooding
Reduced airflow
Thermostat setting
Faulty high- or low-pressure control
Loose wiring
Thermostat
POSSIBLE CAUSE
Incorrect piping
Faulty TEV
REMEDY
In each case, the cure is the same� Recover refrigerant�
Add filter drier, evacuate, and recharge.
REMEDY
Reduce pipe size to improve oil return�
Check system charge�
Repair and recharge�
Observe piping guidelines�
Check crankcase heater�
Check system charge�
Dirty filter
Dirty coil
Wrong duct size
Restricted duct
Advise customer�
Replace control�
Check all control wires�
In supply air stream, out of calibration
Customer misuse
REMEDY
Review pipe size guidelines�
Replace TEV�