Honeywell G0062790 Installation Manuallines page 20

50 hz air-cooled generators
Table of Contents

Advertisement

2. Most applications will require an external manual full flow shutoff valve on the fuel line.
Figure 5.2 — Full Flow Shutoff Valve
3. When connecting the gas line to the generator, use the provided section of UL Listed or AGA-approved flexible fuel line in accordance with
local regulations. The purpose of the flexible fuel line is to ensure that vibration from the generator does not cause a gas leak at one of the
connection points, so it's important that the line be installed with as few bends as possible. Configure the sediment trap (if applicable or
required by code) as illustrated.
Figure 5.3 — Sediment Trap
Figure 5.4 — Incorrect Routing of Flexible Hose
18
SEDIMENT TRAP