Section 3 - Site Selection And Preparation; Site Selection - Honeywell G0062790 Installation Manuallines

50 hz air-cooled generators
Table of Contents

Advertisement

Site Selection and Preparation
Section 3

3.1 SITE SELECTION

These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer's requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
NOTE:
The generator can be placed
under decks or structures as
long as all clearances are met
and local building codes are
followed.
Figure 3.1 – Installation Guidelines
10
No operable windows or openings in the wall permitted
within 1.52 m (5 ft) from any point of the generator.
Existing Wall
1524 mm (60 in)
914 mm
(60 in)
1524 mm (60 in)
Minimum
Generator
457 mm (18 in)
Minimum Distance
Top of Generator
914 mm (36 in)
1524 mm (60 in)
Recommended
1524 mm (60 in)
Clearance from operable
windows, doors or any
914 mm
(36 in)
openings in the wall.
Clearance from the ends and front of the
generator must be 914mm (36 in.). This would
include shrubs, bushes and trees. Clearance
at the top should be a minimum of 914mm (60
in.) from any structure, overhang or projec-
tions from the wall. The generator should not
be placed under a deck or other structure that
is closed in and would limit or constrain air
flow.
NOTE:
Removable fence panels for servicing
cannot be placed less than 457 mm (18 in)
in front of the generator.
457 mm (18 in)
Minimum