When a PKZM0/XTPR...BC1 is to be used for monitoring
an AC or DC motor, the current must flow across all three
current paths in order to avoid early tripping.
Figure 4:
Wiring of the motor-protective circuit-breaker for
the protection of AC or DC motors (bimetallic
release switched in series)
(a section "Auslösekennlinien/Tripping characteristics
PKZM0/XTPR...BC1" auf page 43).

Restarting

After tripping, the bimetallic releases must first cool down
before the motor-protective circuit-breaker can be reset.
h
The PKZM0/XTPR...BC1 motor-protective circuit-breakers
can only be switched on locally.

Test function

Proper functioning of the circuit-breaker can be verified by
means of the testing feature b (a fig. 1, page 28).
The active PKZM0/XTPR...BC1 motor circuit-breaker is
tripped by actuating the test release with the help of a
screwdriver. This allows the user to verify the proper
functioning of the motor-protective circuit-breaker in the
commissioning phase.
Description of device