Installation Requirements; High Elevations; Pressure Test Points; Odor During Operation - Majestic fireplaces UVHK23MP Installation And Operating Instructions Manual

Vermont castings gas log heaters installation and operating instructions
Table of Contents

Advertisement

The fireplace must meet the minimum dimensions listed below. (Fig. 1) Do not install the logset if the fireplace does
not meet these minimums.
Logset
Gas
Width Width Depth
UVHK36MN
Natural
UVHK31MP Propane
UVHK29MN
Natural
UVHK23MP Propane
A. Front width
C. Depth
Fig. 1 Minimum fireplace dimensions.

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration from elevations up to
4,500 feet (1,370m) above sea level.
Nuisance outages may occur at altitudes above
4,500 feet (1,370m) if dirt, dust, lint and/or cob-
webs are allowed to accumulate on burner and/or
ODS pilot. Monthly inspection and cleaning is
recommended for altitudes above 4,500 feet
(1,370m)
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m)
20008056

Installation Requirements

Min. Fireplace Dimensions
A
B
C
D
Front Rear Overall Overall
Height
28"
18"
14¹⁄₂"
17"
28"
18"
14¹⁄₂"
17"
23"
16"
14¹⁄₂"
17"
23"
16"
14¹⁄₂"
17"
D
B
C
A
B. Rear width
FD370-2
D. Height
Fireplace
dimensions/vl18
3/25/99
Inlet Supply
Pressure (w.c.)
Manifold
Min.
Max.
Pressure
5.5"
14.0"
11.0"
14.0"
5.5"
14.0"
11.0"
14.0"
The gas control is equipped with a captured screw-type
pressure test point, therefore it is not necessary to pro-
vide a 1/8" test point upstream of the control.
Neither natural gas nor propane gas give off an odor
when burned. The nature of a vent free combustion
system, however, is such that odors may occasionally
be produced during heater operation when impurities
exist in the immediate area. Cleaning solutions, paint,
solvents, cigarette smoke, candles, adhesives, new car-
pet or textiles, etc., all can create fumes. These fumes
FD370-2
may mix with combustion air and can create odor. Such
odors will disappear over time, however, the condition
can be alleviated by opening a window or otherwise
providing additional ventilation to the area.
This appliance is for installation in a solid-fuel
burning masonry, fireplace with a working flue,
a U.L.-127 listed manufactured solid-fuel burn-
ing fireplace, in any Majestic ventless firebox,
or in any listed ventless firebox enclosure
certified to I.A.S. U.S. Requirement 2-97 or
ANSI Z21.91.
This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventila-
tion air must be provided. Refer to Pages 7 and 8.
BTU/hr.
Low
Med.
Input
Input
3.5"
10,000
22,500 36,000
11.0"
10,000
20,000 31,000
3.5"
16,000
--
11.0"
14,000
--

Pressure Test Points

Odor During Operation

WARNING
NOTICE
High
Air Shutter
Input
Setting
.136" (1)
.136" (2)
29,000
.136" (1)
23,000
.136" (2)
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uvhk29mnUvhk31mpUvhk36mn

Table of Contents

Save PDF