Reading your label Every APG instrument comes with a label that includes the instrument’s model number, part number, serial number, and a wiring pinout table. Please ensure that the part number and pinout table on your label match your order.
Warranty and Warranty Restrictions This product is covered by APG’s warranty to be free from defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit https://www.apgsensors.com/about-us/terms-conditions.
• Specifications Performance Pressure Ranges 0 to 250 PSI Digital Output Modbus RTU, 4-wire RS-485 Over Pressure 2X FSO Burst Pressure 3.0X FSO 1 Year Stability 0.75% FSO Accuracy Linearity, Hystereses & Repeatability ±0.25% of Full Scale (BFSL) up to ±0.1% of Full Scale ±1.0% for ≤...
Power Supply Use Shielded Cable RST-6001 Modbus Controller Equivalent 120 Ω USB to computer terminating resistor with APG Modbus internal to RST-6001 software PT-500 modbus PT-500 modbus PT-500 modbus series sensor series sensor series sensor Note: An independent +5-28 Vdc...
IMPORTANT: APG modbus equipment uses reversed TX+/TX- pins. When making connections between APG equipment, ensure continuity of A to A and B to B pins. When connecting APG modbus equipment to other systems, ensure continuity of TX+ to TX+ and TX- to TX-.
• Removal Instructions Removing your PT-500 from service must be done with care. It’s easy to create an unsafe situation, or damage your sensor, if you are not careful to follow these guidelines: • For sensors installed via NPT process connection, make sure the pressure is completely removed from the line or vessel.
• Modbus Programming with RST-6001 and APG Modbus Software APG RST-6001 Modbus Controller can be used in tandem with APG Modbus to program and control up to 20 PT-500 L5 or PT-500 L31 sensors. Through APG Modbus, you can monitor the raw readings from the sensor, including level or pressure, temperature and battery voltage, or configure the sensor.
Page 12
Holding Registers (0x03) - PT-500 L5 pressure series Register Function Value Range 40400 Device Address 1 to 247 40401 Units 0-16 40402 Application Type 0 or 8 40403 40404 Decimal (Calculated) 0 - 3 40405 Max Pressure *0 - 32,000 PSI 40406 Full Pressure 0 - 32,000 PSI...
Page 13
Holding Registers (0x03) - PT-500 L31 level series Register Function Value Range 40400 Device Address 1 to 247 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 0 - 11 40403 Volume Units 1 - 7 40404 Decimal (Calculated) 0 - 3...
40403 - Volume Units Determines the units of measure for the calculated reading when Application Type is set to 2 - 6 or 9 -11. 1 = Feet 5 = Liters 2 = Million Feet 6 = Inches 3 = Gallons 7 = Barrels 4 = Meters •...
Page 16
Application 3 - Volume of Standing Cylindrical Tank ± Conical Bottom Register Function Value Range Diameter 40400 Device Address 1 to 247 40401 Units 40402 Application Type 40403 Volume Units 1 - 7 40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406...
Page 17
Application 5 - Volume of Horizontal Cylindrical Tank ± Hemispherical Ends Register Function Value Range 40400 Device Address 1 to 247 40401 Units 40402 Application Type 40403 Volume Units 1 - 7 40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level...
Page 18
Application 7 - Pounds (Linear Scaling) Register Function Value Range 40400 Device Address 1 to 247 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 40403 Volume Units 40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406...
Page 19
Application 10 - Volume of Horizontal Oval Tank Register Function Value Range 40400 Device Address 1 to 247 40401 Units 40402 Application Type 40403 Volume Units 1 - 7 40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm...
• Vent Tube Drying Condensation in the vent tube can damage the electronics in your sensor, resulting in unreliable readings. APG offers two methods of preventing vent tube condensation: a venting cap, and a desiccant drying cartridge. The venting cap is a PVC tube with a hydrophobic patch that allows moisture to pass out of the tube without allowing water in (See Figure 4.1).
Figure 4.1 Figure 4.2 NOTE: Desiccant crystals change from blue to pink as they become saturated. Car- tridge must be replaced when all crystals have saturated. • Repair and Returns Should your PT-500 series pressure transmitter require service, please contact the factory via phone, email, or online chat.