E.S.P.(External Static Pressure) Setting

Open the rear cover of the wired remote-controller to set the mode.
Select one of three selectable modes as follows.
I Without Zone System
1. Position V-H, F-H:
• This position sets the maximum E.S.P as a default set.
2. Position V-L:
• This position sets the minimum E.S.P as a default set.
I With Zone System
1. Position V-H:
• Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
• Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of
dampers.
3. Position V-L:
• Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
*Maximum: 30k(H/P)-10mmAq, 30k(C/O)/36k/42k-8mmAq, 48k/60k-15mmAq
Minimum: All-0mmAq
Move the slide switch to set position.
Slide switch for zone state/Default E.S.P
Close the rear cover and check if it works normally.
CAUTION:
• Select the position after checking duct work and E.S.P of the unit.