Refrigerant Piping Work
5.
Charging refrigerant

1-1. Charging additional refrigerant

• If the total length of refrigerant piping exceeds 20m, add refrigerant. (The maximum total length of refrigerant piping for all
rooms is 30m.)
A
g=20X
1-2. Completely recharging refrigerant
• The total amount that must be added is the amount listed on the machine nameplate and the amount of the additional
refrigerant.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases.
Do not vent gases into the atmosphere.
R32
Refrigerant type:
(1)
GWP
value:
675
Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged in the field and
the total refrigerant charge
tCO
eq calculation according to the formula (rounded up
2
to 2 decimal places)
on the refrigerant charge label supplied with the product.
NOTE
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit.
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.
NOTICE
In Europe, the greenhouse gas emissions of the total refrigerant charge in the system (expressed as tonnes CO
is used to determine the maintenance intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label. This GWP value is based on the 4th IPCC Assessment
Report. The GWP value mentioned in the manual might be outdated (i.e., based on the 3rd IPCC Assessment Report).
CAUTION
• Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
• Do not overfill with refrigerant. This will break the compressor.
Precautions for compressor
Electric shock hazard
• Use this compressor on a grounded system only.
• Turn power OFF before servicing.
• Replace terminal cover before applying power.
Injury hazard
• Wear protective goggles.
Explosion or fire hazard
• Use tubing cutter to remove compressor.
• Do NOT use torch. System contains refrigerant under pressure.
• Do NOT drive under air or vacuum condition.
• Use only approved refrigerants and lubricants.
Burn hazard
• Do NOT touch with bare hands during or immediately following operation.
English
A: Amount to add
B
B: Length of refrigerant piping minus 20. (Total for all rooms)
(1)
GWP = global warming potential
WARNING
The filled out label must be adhered in the
proximity of the product charging port
(e.g. onto the inside of the stop valve cover).
Contains fluorinated greenhouse gases
1
=
GWP: 675
2
=
2
1
1
+
2
=
GWP × kg
=
1000
5
6
factory refrigerant charge of the
product:
see unit name plate
additional refrigerant amount
charged in the field
total refrigerant charge
kg
greenhouse gas emissions of the
total refrigerant charge expressed
kg
as tonnes CO
-equivalent
2
refrigerant cylinder and manifold
for charging
kg
outdoor unit
tCO
eq
2
-equivalent)
2
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

2mxm50m2v1b92amxm40m3v1b2amxm50m3v1b

Table of Contents