Download Print this page
VDH ALFA 72-VS User Manual

VDH ALFA 72-VS User Manual

Differential thermostat

Advertisement

Quick Links

User manual
ALFA 72 VS 0-20
Differential Thermostat.
VDH doc. 080333
Software;
992903 ALFA 52/72 VS 20 -50..+50
100320 ALFA 52/72 VS 20 -20..+80
992901 ALFA 52/72 VS 20 0..+100
* Installation.
On the connection diagram of the ALFA 72-VS is shown how the sensors, power supply and relays
has to be connected. After connecting the ALFA 72-VS to the power supply, a self test function is
started. As this test is finished, the measured differential temperature of sensor-1 minus sensor-2
appears in the display.
* Control.
The ALFA 72-VS thermostat can be controlled by four pushbuttons on the front These keys are:
SET
- view / change set point and reset the alarm
 (UP)
- increase the set point.
 (DOWN) - decrease the set point.
 C
- hidden key under unit symbol
* Viewing the temperature from sensor-1 and sensor-2.
By pressing the UP and DOWN keys simultaneously and after that the UP key, the measured value
from sensor-1 can be read-out. If the down key is pressed, the measured value from sensor-2 is
shown. If no key is pressed for a few seconds, the differential temperature is shown again.
* Viewing the delta-setpoint.
Viewing set point delta thermostat:
By pushing the SET key, the set point of delta thermostat appears in the display.
A few seconds after releasing the keys the set point disappears and the differential temperature is
shown again in the display.
* Changing the delta-setpoint.
Push the SET key. The delta-setpoint appears in the display. Release the SET key. Now push the SET
key again together with the UP or DOWN keys to change the set point. A few seconds after releasing
the keys, the measured differential temperature is shown again in the display.
* Status of the Relays.
By pushing the hidden  C key the display shows the status of the relays. Each digit shows the status
of one relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2 are on and relay 3
is off.
Relays 1 and 2 are used for the differential thermostat (see function diagram).
Relay 3 is used as an alarm relay.
O
C
Version: v1.2
File: Do080333.wpd
Typenr. 904.000702
Typenr. 904.000925
Typenr. 904.000678
1
Date: 22-04-2010
Static range (see sticker);
-50/+50,0  C
-20/+80,0  C
0/+100,0  C

Advertisement

loading
Need help?

Need help?

Do you have a question about the ALFA 72-VS and is the answer not in the manual?

Questions and answers

Summary of Contents for VDH ALFA 72-VS

  • Page 1 On the connection diagram of the ALFA 72-VS is shown how the sensors, power supply and relays has to be connected. After connecting the ALFA 72-VS to the power supply, a self test function is started. As this test is finished, the measured differential temperature of sensor-1 minus sensor-2 appears in the display.
  • Page 2 * Setting internal parameters. Next to the adjustment of the set point, internal settings can be made like differential, sensor offset, set point range and the functions of the thermostat. Push the DOWN key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left display the upper and lower segment are blinking.
  • Page 3 Indicates a open-circuit of Sensor-2 and Sensor-1 okay H - L Indicates Sensor-1 with a open-circuit and Sensor-2 with a short-circuit * Technical data ALFA 72-VS. Type : ALFA 72-VS Differential thermostat : Differential temperature in display: 0/+20  C (0,1) Range : -50/+50,0 ...
  • Page 4 * Function diagram. * Dimensions. * Connections. * Address VDH Products BV Tel: +31 (0)50 - 30 28 900 Produktieweg 1 Fax: +31 (0)50 - 30 28 980 9301 ZS Roden Email: info@vdhproducts.nl Nederland Internet: www.vdhproducts.nl...