1 Function
The ALFA(NET) 71 is a panel mount thermostat-unit. The thermostat has also three relays outputs
selectable for function cooling, heating or alarm. The temperature is measured by sensor-1 unless
sensor-2 is active as control sensor (P05=1), in this case the average temperature of both sensors
(SM 811 2-wire) is displayed and used for control.
The ALFANET 71 is provided with an RS-485 network connection allowing to read out and set this
unit on the ALFANET.
2 Installation
On the connection diagram of the ALFA(NET) 71 is shown how the sensor(s), power supply, relays,
and optional network should be connected. After connecting the ALFA(NET) 71 to the power supply,
a self-test program is started. As the test is finished the measured temperature appears in the
display.
3 Control
The ALFA(NET) 71 thermostat can be controlled by four pushbuttons on the front.
These keys are;
SET
8
UP
π
DOWN
°C
STATUS
Description:
Alfa(net) 71 12Vac 0/+100°C
Type:
Manual
File:
Do170982 ALFANET 71 0_+100°C Flash
V10 EN.docx
VDH Products BV
User manual
0/+100°C
- view / change the set value and reset alarm.
- increase the set value.
- decrease the set value.
- relay status key.
ALFA(NET) 71
Pages:
8
By:
BVDB
Paraph:
Doc. No.:
170982
Version:
1.0
Date:
17-08-2017

Advertisement

loading
Need help?

Need help?

Do you have a question about the ALFANET 71 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for VDH ALFANET 71

  • Page 1 (P05=1), in this case the average temperature of both sensors (SM 811 2-wire) is displayed and used for control. The ALFANET 71 is provided with an RS-485 network connection allowing to read out and set this unit on the ALFANET.
  • Page 2 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 4 View set point By pushing the SET key the set point appears in the display. The decimal point of the most right display starts blinking. A few seconds after releasing the SET key the set point disappears and the measured temperature is shown again in the display.
  • Page 3: Error Messages

    E.. and – L – at an short circuit of the sensor or E.. and – H – at an interrupted circuit of the sensor. 10 Technical data Type ALFA 71 0/+100°C or ALFANET 71 0/+100°C Range 0/+100°C uitlezing per 0,1°C Supply 12 Vac 50/60Hz, 3VA (-5…+10%)
  • Page 4 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 11 Setting internal parameters Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset, setpoint range and the functions of the thermostat. Push the DOWN key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left display the upper- and lower-segment are blinking.
  • Page 5 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 Para- Description Range Default meter value Readout on whole degrees 0 = No, 1 =Yes Alarm type 0 = None 0 .. 2 1 = Absolute 2 = Relative Minimum alarm set point 0.0 ..
  • Page 6 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 12 Function diagram Pagina 6 van 8...
  • Page 7 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 13 Connections Pagina 7 van 8...
  • Page 8 ALFA(NET) 71 0/+100°C Document No.: 170982 Version 1.0 14 Dimensions 15 Address Tel.: +31 (0)50 – 30 28 900 VDH Products B.V. Productieweg 1 Fax.: +31 (0)50 – 30 28 980 9301 ZS Roden Email: info@vdhproducts.nl The Netherlands Internet: www.vdhproducts.nl...