Setting Up the Standalone System

Flushing and Filling
When installing any Heat pump, we insist on a thorough system flush
prior to connection in line with the Building Regulations for England
and Wales, Part L, 2006. Using the power flusher fill the system with
water and 25% Propylene Glycol, there is no pressure sensor in the
unit so we can operate from 0 -3 bar maximum.
Before Power Up
The Outdoor Unit
The outdoor unit does not need any settings made, its ready to go
from the factory.
The FTC5 control box
The FTC5 control box needs the following dip switches set:
SW1-1 off no boiler
SW1-2 off max hot water temp to 55c
SW1-3 on for DHW tank
SW1-4 on immersion heater
SW1-7 on for monoblock unit
SW2-1 off for remote thermostat
SW2-8 on for flow switch
SW3-5 on to allow heating
SW3-7 off coil for HW cylinder
SW4-1 off deactivate multi controllers