Dorner 1100 Series Operation Manual

Dorner 1100 Series Operation Manual

Remote signal brushless dc controller
Hide thumbs Also See for 1100 Series:

Advertisement

Quick Links

1100 Series Remote Signal
Brushless DC Controller
DORNER MFG. CORP.
P.O. Box 20 • 975 Cottonwood Ave.
Hartland, WI 53029-0020 USA
851-756 Rev. B
Operation Manual
For other service manuals visit our website at:
www.dorner.com/service_manuals.asp
INSIDE THE USA
TEL: 1-800-397-8664
FAX: 1-800-369-2440
OUTSIDE THE USA
TEL: 262-367-7600
FAX: 262-367-5827

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1100 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Dorner 1100 Series

  • Page 1 1100 Series Remote Signal Brushless DC Controller Operation Manual DORNER MFG. CORP. INSIDE THE USA OUTSIDE THE USA P.O. Box 20 • 975 Cottonwood Ave. TEL: 1-800-397-8664 TEL: 262-367-7600 Hartland, WI 53029-0020 USA FAX: 1-800-369-2440 FAX: 262-367-5827 For other service manuals visit our website at: www.dorner.com/service_manuals.asp...
  • Page 2: Table Of Contents

    Dorner’s Limited Warranty applies. IMPORTANT Dorner 1100 series conveyors have patents pending. Some illustrations may show guards Dorner reserves the right to make changes at any time removed. DO NOT operate equipment without notice or obligation. without guards. Dorner has convenient, pre−configured kits of Key Service Parts for all conveyor products.
  • Page 3: Warnings - General Safety

    PINCH POINTS and other mechanical hazards before system start-up. A DANGER Hazardous voltage will cause severe injury or death. LOCK OUT POWER BEFORE WIRING. 1100 Series Remote Signal Brushless DC Controller 851-756 Rev. B Dorner Mfg. Corp.
  • Page 4: Operations

    For customer supplied wiring: • Use shielded, multi-conductor cable for input signal. • Wires to be AWG26 minimum. • Shield of multi-conductor cable should be grounded to sub panel. 1100 Series Remote Signal Brushless DC Controller Dorner Mfg. Corp. 851-756 Rev. B...
  • Page 5: Setting The Running Speed

    The motor speed range is from 100 to 3000 rpm for Adjust desired accel/decel at driver (Figure 2, item 1). the case of the motor alone. Dorner speed ranges are 100 to 2500 rpm for constant motor torque. Figure 2...
  • Page 6: Setting By External Potentiometer

    Wire START/STOP, COM, and CW/CCW to terminal (Figure 4, item 2). Install motor cord through interface location (Figure 4, item 3). Refer to Motor Manual 851-748 or 851-749 for details. 1100 Series Remote Signal Brushless DC Controller Dorner Mfg. Corp. 851-756 Rev. B...
  • Page 7: Speed Control With External Potentiometer (Customer Supplied)

    (Figure 8, item 2), as shown in (Figure 7). USED LT. BLU Install motor cord through interface location (Figure 8, item 3). Refer to Motor Manual 851-748 or 851-749 Figure 7 for details. 1100 Series Remote Signal Brushless DC Controller 851-756 Rev. B Dorner Mfg. Corp.
  • Page 8: Setting By External Dc Voltage

    Figure 10 TERMINAL START/STOP BLOCK CW/CCW EXTERNAL DC POWER SUPPLY 0 TO 5 VDC 1 mA OR MORE USED LT. BLU Figure 10 1100 Series Remote Signal Brushless DC Controller Dorner Mfg. Corp. 851-756 Rev. B...
  • Page 9 5 as shown in (Figure 10). Install motor cord through interface location (Figure 12, item 3). Refer to Motor Manual 851-748 or 851-749 for details. 1100 Series Remote Signal Brushless DC Controller 851-756 Rev. B Dorner Mfg. Corp.
  • Page 10: Return Policy

    RMA will automatically close 30 days after being issued. To get credit, items must be new and undamaged. There will be a return charge on all items returned for credit, where Dorner was not at fault. It is the customer’s responsibility to prevent damage during return shipping.