Diagnostic aid / Heating body
JS
1. Preliminary checks to be carried out
In the case of a drop in the boiler output, for example hot water not hot enough, although the
settings have not been changed:
Check the gas supply pressure,
Check that the siphon and the condensate discharge pipe are clean,
Flue gas discharge and the air supply pipes: Check that the pipe and the terminal are empty along their entire length,
Check the Ohmic value of the sensors (DHW sensor, Tank sensor,...),
MCA 25/28 BIC and MCA 25/28 MI : Check the state
- of the plate exchanger : clean it if required
- of the water filter cartridge : clean it if required.
2. Heating body checking procedure
If all the above-mentioned causes have been eliminated, check the condition of the burner and
the heating body using the following procedure:
1. Check the boiler type and the gas type indicated on the rating plate:
2. Check the value of parameter MAX.VENT.BOIL (in menu #PRIMARY LIMITS) and correct it if necessary (See
values in APPENDIX hereafter).
Q
N° IT2652C-en
T001539-B
1/7
EN
09/05/2022
IT2652C-en

Advertisement

loading

Summary of Contents for DeDietrich MCA 10

  • Page 1 Technical Information MCA 10, MCA 15, MCA 25 MCA 25/28 MI, MCA 25/28 BIC, MCA 35 Wall-hung gas condensing boilers Diagnostic aid / Heating body N° IT2652C-en 09/05/2022 1. Preliminary checks to be carried out In the case of a drop in the boiler output, for example hot water not hot enough, although the...
  • Page 2 Gas L (G25) Propane (G31) Values at full load PMAX MAX.VENT.BOIL MAX.VENT. BOIL MAX.VENT. BOIL Diaphragm (For France) Ø mm (1)(2) MCA 10 3300 3300 3200 4.7 - 5.2 4.4 - 4.9 4.7 - 5.2 3.00 (1)(2) MCA 15 4500...
  • Page 3 (Settings for France. For the other countries: Refer to the instruction manual delivered with the boiler) Gas H (G20) Gas L (G25) Propane (G31) Values at low load PMIN MIN.VENT. MIN.VENT. MIN.VENT. (For France) MCA 10 1800 1800 2200 - 6.3 - 6.1 - 6.1 MCA 15 1800 1800 2200 - 6.3...
  • Page 4 Table 1 : Control values: G20/G25 G20/G25 BE G31 CH G20 CH Gas type: MAX.VENT. (rpm) 3300 3200 3300 3200 3300 MCA 10 Control pressure (mbar) MAX.VENT. (rpm) 4500 4400 4500 3600 4500 MCA 15 Control pressure (mbar) MAX.VENT. (rpm)
  • Page 5 5. In order to determine the actual control pressure, Proceed as follows: a) Set the boiler to holiday mode ( ) using the MODE key and the rotary button, to supress any heating demand. b) Use an electronic pressure gauge, which will allow to measure a negative pressure (depression).
  • Page 6: Spare Parts

    3. Spare parts Boiler type Reference to order in spare parts MCA 10 MCA 15 7701124 Heating body - MCA 25 (All countries) MCA 25/28 MI MCA 25/28 BIC MCA 35 7701123 Heating body - (All countries) CAUTION: Chemical cleaning and/or mechanical cleaning of the new heat exchanger is prohibited !
  • Page 7 RPM to the values indicated below, according to the boiler and gas type: The settings given below are for France. For other countries: Refer to the instruction manual delivered with the boiler. • MCA 10 Unit Gas H (G20) Gas L (G25)