Download Print this page
Honeywell NOTIFIER 020-772 Fitting Instructions
Honeywell NOTIFIER 020-772 Fitting Instructions

Honeywell NOTIFIER 020-772 Fitting Instructions

4-way sounder pcb

Advertisement

Quick Links

The 4-Way Sounder PCB (kit PN: 020-772) supports four configurable monitored outputs and two configurable digital
inputs. Various preset combinations of input and output functions are selected via a DIP switch. Up to two,
independently-configurable 4-Way Sounder PCBs may be fitted in the fire control panel. Provision is made for
connecting an SST LED box.
Output options are: sounder, ÜE transmission circuit, SST extinguishing system (three output circuits are used: one
for SST output and two for SST inputs), fault routing or fire routing. To connect an SST, a Routing Termination kit (PN:
020-773) and LED Display Box (English version PN: 020-769-001 or German version 020-769) are also required. The 4-
Way Sounder PCB detects partial open and short circuits on the output circuits, to meet EN54-13 requirements.
Input options are: fire transmission confirmed, fault transmission confirmed, class change or day mode.
Depending upon its output load, the PCB can be powered from the panel or from an external dc power supply, as set by a
jumper link.
OBSERVE PRECAUTIONS FOR
OBSERVE PRECAUTIONS FOR
HANDLING ELECTROSTATIC
HANDLING ELECTROSTATIC
Your 4-Way Sounder PCB Kit, PN: 020-772 should
contain:
4-Way Sounder PCB
16-way Ribbon Cable (x1)
Nylon Spacers (x2)
Nylon locking rivets (x2)
C C
D D
4 4
F F
M a i n P
7 7
ATTENTION
ATTENTION
SENSITIVE DEVICES
SENSITIVE DEVICES
PN: 124-372
PN: 082-252-002
PN: 423-262
PN: 423-261
1 1
3 3
M a in
M a in
P C B
P C B
B B
1
0
2 2
A A
E E
H H
C B
G G
9 9
For clarity,
For clarity,
batteries are
batteries are
not shown.
not shown.
Fitting/Replacing the 4-Way Sounder PCB
Check your equipment....
Take suitable anti-static precautions, such as wearing a grounded
wrist strap, when following ALL instructions. Remove all packaging
from the kit and ensure that it has not been damaged in transit (and
that no items are missing - see checklist on the left) before
proceeding any further. If no damage is evident, proceed using the
instructions below. In the unlikely event that damage has occurred
or items are missing, DO NOT PROCEED, contact your supplier
and refer to the panel's Installation, Commissioning &
Procedure for Fitting/Replacing the 4-Way Sounder
PCB
To fit/replace the 4-Way Sounder PCB, configure it (see page 3), then
proceed as follows:
1 Only carry out this procedure when mains power to the panel has been
isolated.
2 Use a 4mm hex key to release the two socket-headed screws (A) that
secure the cover (B) to the back box (C).
3 Carefully withdraw the cover from the back box. Store cover safely.
4 Ensure the batteries (D) are disconnected.
5 If replacing the 4-Way Sounder PCB, temporarily disconnect all
external cables to the Main PCB.
Removing the Main PCB
6 Disconnect the earth lead from the right-angled, blade connector (E)
located at the top right-hand corner of the Main PCB.
7 Carefully push up the two PCB-retaining clips (F) until the top edge of
the Main PCB is free to move - the bottom edge of the PCB is still
located by the three tabs (G).
Note: If a 2-Way Relay PCB is fitted, slide it to the left to disengage
socket connector SK2 on the Main PCB. Once disengaged, there
is no need to remove the 2-Way Relay PCB from the panel.
8 Leave the ribbon cable connected at connector SK4 (H) on the Main
PCB, disconnect the ribbon cable at socket connector SK2 on the PSU
PCB.
DO NOT forget to reconnect this cable before re-fitting the main
PCB.
9 Gently pull the top of the Main PCB away from the back box and lift the
PCB clear of the back box and store safely.
1
997-536-000-2, Issue 2 July 2009

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER 020-772

  • Page 1 Fitting/Replacing the 4-Way Sounder PCB The 4-Way Sounder PCB (kit PN: 020-772) supports four configurable monitored outputs and two configurable digital inputs. Various preset combinations of input and output functions are selected via a DIP switch. Up to two, independently-configurable 4-Way Sounder PCBs may be fitted in the fire control panel. Provision is made for connecting an SST LED box.
  • Page 2 Fitting/Replacing the 4-Way Sounder PCB Fitting the 4-Way Sounder PCB Follow steps 10 to16 if only fitting one 4-way Sounder PCB. If fitting two 4- way Sounder PCBs follow steps 10 and 11 then go step 17 before continuing with steps 12 - 16. With the Main PCB removed..
  • Page 3 Fitting/Replacing the 4-Way Sounder PCB Configuration Options 1: PSU Jumper 2: External PSU Link Earth Link By default, the PCB is configured as follows: All circuits are sounders, activated on first fire, any zone. Sounders steady Position A: Sounder PCB is If an external PSU with its output powered from panel via ribbon cable.
  • Page 4 Fitting/Replacing the 4-Way Sounder PCB External Wiring Configurable Circuits External Power SST LED Box Input Typical wiring examples are given below. The functions available on a Connection particular circuit are determined by the configuration options described on This connection is provided the previous page.