E54C3C Installation Guide
Configuration (cont.)
Configuration Menu
All parameters in the configuration menu are modified in one of two ways.
1. Select a value from a pre-set list: use the down button to scroll through the parameter values until the desired value is
reached. Press OK to confirm the selected value.
2. Modify a numerical value: the digit on the far right is selected first. Use the down button to modify the selected digit.
Press OK to move to the next digit. Repeat for all available digits, then press OK to confirm the selected value.
To cancel the current entry, press the ESC button. This cancels the modification and the screen reverts to the last saved value.
ESC
Wiring
Wiring\Type
OK
3PH4W
1PH2W L-N
...
CT & VT Ratio
OK
..\CT Secondary
5
1
Frequency
OK
Frequency
50
60
Date
Date
OK
1
2 ...
DD-MM-YYYY
Time
OK
Time
1
2 ...
hh:mm
Multi- Tariffs
OK
..\Control Mode
Disable
by Digital Input
by Communications
by Internal Clock
Overload Alarm
OK
..\Alarm
Disable
Enable
OK
Digital Output
..\DO Function
Disable
for Alarm
for Pulse
Digital Input
OK
..\DI Function
Input Status
Tariff Control
Partial Reset
Input Metering
OK
Communication
..\Slave Address
1
2 ...
1-247
OK
Com.Protection
Com.Protection
Enable
Disable
Contrast
OK
Contrast
1
2
...
Password
OK
Password
1
1 - 9999
OK
Reset Config
Reset Config
Confirm & Reboot?
After performing basic configuration, navigate to the real-time data screens and verify that the readings are correct.
The terms "VT" (voltage transformer) and "PT" (potential transformer) are used interchangeably.
ZL0131-0G
Page 7 of 8
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
EAV71194-04
A - Cancel and return to the
ESC
ESC
ESC
Wiring\VT
Wiring\CT
Wiring
OK
OK
OK
OK
Save settings?
B - Reset the settings to their
Direct-NoPT
1 CT on I1
Wye(3PTs)
2 CTs on I1, I3
...
...
OK
..\CT Primary
OK
..\VT Secondary
OK
..\VT Primary
OK
CT & VT Ratio
OK
Save settings?
1
2 ...
100
1
2 ...
110
0 - 99999
...
0 - 9999999
OK
Frequency
OK
Save settings?
Date
OK
OK
Save settings?
OK
Time
OK
Save settings?
T3 Start = T1 Start
T4 Start = T2 Start
Multi Tariffs
OK
Save settings?
OK
OK
OK
OK
..\Schedule
..\T1 Start
..\T2 Start
by 2 Tariffs
1
2 ...
1
2 ...
by 3 Tariffs
...
hh:mm
hh:mm
OK
Overload Alarm
Save settings?
OK
..\Pick Up Value
OK
1
2 ...
0 - 9999999
Digital Output
OK
Save settings?
OK
OK
..\Pulse Constant
..\Pulse Width
OK
0.01
100
0.1
200
...
...
Digital Input
OK
Save settings?
OK
..\In. Pulse Const.
OK
1
2 ...
1 - 99999
OK
OK
OK
OK
..\Baud Rate
..\Parity
Communication
Save settings?
19200
ODD
38400
EVEN
...
NONE
OK
OK
Com.Protection
Save settings?
OK
Contrast
OK
Save settings?
OK
Password
OK
Save settings?
2 ...
OK
E54C3C Installation Guide
TM
Multi-Tariff Feature
previous screen
defaults, except for the
password, and restart the
meter.
Troubleshooting
0818
ZL0131-0G
Page 8 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
EAV71194-04
The multi-tariff feature allows the meter to categorize energy consumption by peak times vs. off-peak times and by weekdays
vs. weekends. The following table illustrates how the tariffs operate according to the tariff selection (2, 3 or 4 tariffs). These
tariffs are stored in four different registers: T1, T2, T3, and T4.
2 Tari s
T1
T1
Weekday
T2
24 H
T1
Weekend
T2
24 H
Code
Description
LCD display is not visible.
-
Push buttons do not function.
-
Metering stops due to an EEPROM error. Press OK to
101
display total energy consumption.
Metering stops due to a lack of a calibration table. Press
102
OK to display total energy consumption.
Metering continues. Mismatch between frequency
201
settings and frequency measurements.
Metering continues. Mismatch between wiring settings
202
and wiring inputs.
Metering continues. Phase sequence reversed.
203
Metering continues. Total active energy negative due to
204
incorrect voltage and current conditions.
Metering continues. Date and Time have been reset due to
205
a loss of power.
Metering continues. Pulse is missing due to overload on
206
energy pulse output.
Metering continues. Abnormal internal clock function.
207
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
TM
3 Tari s
4 Tari s
T1
T2
T2
24 H
24 H
T3
T3
T4
24 H
24 H
Solution
Check and adjust LCD contrast.
Restart the energy meter by powering off and powering on
again.
Enter configuration mode and implement Reset Config.
Enter configuration mode and implement Reset Config.
Correct the frequency settings according to the nominal
frequency of the power system.
Correct the wiring settings according to the wiring inputs.
Check the wire connections and correct the wiring settings if
needed.
Check wire connections.
Set the Date and Time.
Check the energy pulse output settings.
Restart the energy meter by powering off and powering on
again then reset the date and time.
0818