E54C3C Installation Guide
Product Diagram
A
B
C/- DI
N.C.
C
DO
N.C.
L
ON
K
5000
/kWh
V1
V2
V3
Vn
J
A. Digital input
B. Digital output
C. RS-485 communications port
D. Communications LED
E. Display for measurement and configuration
F. 1 A or 5 A current transformer input
G. Cancellation
Installation
1. Disconnect power prior to the installation. Use a properly rated voltage sensing device to ensure power is off.
2. Install the meter onto standard DIN rail as shown.
3. Wire the meter (see the Wiring section).
4. Reconnect power to the meter.
5. Configure the meter (see the Configuration section).
ZL0131-0G
Page 3 of 8
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
EAV71194-04
C
D
E
0V
O
D0/- D1/+
RS485
N
OK
ESC
Reset
Config
(I1)
(I2)
(I3)
S1
S2
S1
S2
S1
S2
F
I
H
G
H. Confirmation
I. Selection
J. Voltage inputs
K. Energy pulse LED (5000 flashes per kWh)
L. Status LED (on/off/error)
M. Locking points
N. Lockable covers
Click!
E54C3C Installation Guide
TM
Wiring
M
ES C
O K
0818
ZL0131-0G
Page 4 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
EAV71194-04
For all terminals, apply the correct torque (see below).
V1, V2, V3, N
24 to 14 AWG (0.2 to 2.5 mm
2
)
4.4 in-lb (0.5 N-m) max.
DI, DO, C, C/-
25 to 16 AWG (0.14 to 1.5 mm
)
4.4 in-lb (0.5 N-m) max.
2
I1, I2, I3
18 to 10 AWG (0.8 to 6 mm
2
)
7.0 in-lb (0.8 N-m) max.
Modbus RS-485
24 to 14 AWG (0.2 to 2.5 mm
2
)
4.4 in-lb (0.5 N-m) max.
Digital Input, Digital Output, and Communications Wiring
Digital output wiring is not polarity sensitive.
S
11 to 40 Vdc
5 to 40 Vdc
- /+
+/ -
-
+
Load
0V
S
D0/- D0/+
RS-485
+
C
DIn
C
DOut
CT Wiring
Clearly label the device's disconnect circuit mechanism and install it within easy reach of the operator. Use fuses/circuit
breakers that are rated for the installation voltage and sized for the available fault current. A fuse for neutral is required if the
source neutral is not grounded.
1 Phase
1 Phase, 2-Wire, L-N
1 Phase, 2-Wire, L-L
(I1)
(I2)
(I3)
(I1)
(I2)
V1 V2 V3 Vn
V1 V2 V3 Vn
Fuses and
Shorting
Fuses and
Shorting
Disconnect
Block
Disconnect
Block
S1
S2
S1
S2
L
L1
N
L2
≤ 277 V L-N
≤ 480 V L-L
1 Phase, 4-Wire, Multi-L with N, 2 CTs
1 Phase, 4-Wire, Multi-L with N, 3 CTs
(I1)
(I2)
(I3)
V1 V2 V3 Vn
V1 V2 V3 Vn
Fuses and
Shorting
Fuses and
Disconnect
Block
Disconnect
S1
S2
S1
S2
L
N
L
≤ 277 V L-N
N
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
TM
0 V
Modbus RS-485
D0 = A' / Rx-, A / Tx-
D0 = B' / Rx+, B / Tx+
1 Phase, 3-Wire, L-L-N
(I3)
(I1)
(I2)
(I3)
V1 V2 V3 Vn
Fuses and
Shorting
Disconnect
Block
S1
S2
L1
S1
S2
L2
N
≤ 277 V L-N
≤ 480 V L-L
(I1)
(I2)
(I3)
Shorting
Block
S1
S2
S1
S2
S1
S2
≤ 277 V L-N
0818