SPX Cooling Technologies MARLEY MH MHF702 User Manual page 27

Fluid cooler
Table of Contents

Advertisement

Note
Maintenance
Clean and disinfect cooling tower with biocides. Systems with biofouling,
high general bacterial counts, or positive cultures of legionella may require
additional cleaning. Refer to "Fluid Cooler Cleaning" section—page 21.
Consult your water treatment expert as to prudent biological evaluation
testing.
Geareducer models used on MH Fluid Coolers are designed for 5-year
oil change intervals. To maintain five-year change intervals, use only
oil designed specifically for these Geareducers. If, after five years,
turbine-type mineral oil is used, the oil must be changed semiannu-
ally. Refer to the Geareducer User Manual for oil recommendations
and further instructions.
annually: Relubricate motor(s) according to the manufacturer's instruc-
tions. See instructions on the next page for towers with the motor located
outside the plenum option.
Check to see that all bolts are tight in the fan and mechanical equipment
region, including the fan cylinder and fan guard. Refer to Component User
Manuals for torque values.
Inspect the fluid cooler thoroughly, making maximum use of instructions
given in the separate user manuals. Check structural bolted connections
and tighten as required. Make preventive maintenance repairs as neces-
sary.
Every 5 Years: If equipped, change Geareducer oil. Refer to the Geareducer
User Manual for instructions.
Motor relubrication instructions
Motor located outside plenum option. Double-flow models MHF706 and
MHF707 only.
Open and lock out disconnect switch to make certain motor cannot
be started.
1. Remove guard as shown in Figure 4. Opposite end motor bearing is
accessible from outside the tower.
2. Remove grease fill and relief plugs at both shaft extension end and
opposite end bearings and remove hardened grease, using clean
27