Gossen MetraWatt MAVOWATT 210 Operating Instructions Manual
Hide thumbs Also See for MAVOWATT 210:

Advertisement

Quick Links

Operating Instructions
MAVOWATT 210
3-447-112-03
Three-phase Power and Energy Logger
2/5.22
Download
software
"Dran-View XP"

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MAVOWATT 210 and is the answer not in the manual?

Questions and answers

Summary of Contents for Gossen MetraWatt MAVOWATT 210

  • Page 1 Operating Instructions MAVOWATT 210 3-447-112-03 Three-phase Power and Energy Logger 2/5.22 Download software “Dran-View XP”...
  • Page 2: Table Of Contents

    MAVOWATT 210 Gossen Metrawatt GmbH Contents Safety Precautions............1 Applications ..............3 2.1 Intended Use / Use for Intended Purpose..........3 2.2 Use for Other than Intended Purpose ..........3 2.3 Liability and Guarantee ................ 3 2.4 Opening the Instrument / Repairs ............4 Documentation..............
  • Page 3 MAVOWATT 210 Gossen Metrawatt GmbH 8.6 Saving Measurement Results ............45 8.7 Manage Recorded Data in Dran-View XP .......... 45 Maintenance ..............48 9.1 Cleaning.................... 48 9.2 Maintenance ..................48 9.3 Troubleshooting ................48 9.4 Repair ....................48 9.5 Calibration..................49 10 Contact, Support and Service ........50...
  • Page 4: Safety Precautions

    MAVOWATT 210 Gossen Metrawatt GmbH Safety Precautions General Observe this documentation, in particular all included safety information, in order to protect yourself and others from injury, and to prevent damage to the instrument. • Carefully and completely read and adhere to these operating instructions.
  • Page 5 Gossen Metrawatt GmbH MAVOWATT 210 • The instrument and the included accessories may only be used for the tests/measurements described in the instrument‘s documentation. Electricity • Installation, operation, and maintenance of this instrument must be per- formed by qualified personnel only.
  • Page 6: Applications

    600 VRMS are measured, potential transformers (PTs) or other transduc- ers must be used. Being connected to MAVOWATT 210, flexible AC current probes based on the Rogowski principle or hinged current transformers (CT) are used to measure AC current. The flexible probe allows current measurements on conductors that are hard to reach.
  • Page 7: Opening The Instrument / Repairs

    Gossen Metrawatt GmbH MAVOWATT 210 Opening the Instrument / Repairs The instrument may only be opened by authorized, trained personnel in order to ensure flawless, safe operation and to assure that the guarantee isn’t ren- dered null and void. Even original replacement parts may only be installed by authorized, trained personnel.
  • Page 8: First Steps

    MAVOWATT 210 Gossen Metrawatt GmbH First Steps 1. Read and adhere to the product documentation. In particular observe all safety information in the documentation, on the instrument and on the packaging.  "Safety Precautions" 1  "Applications" 3  "Documentation" 4 2.
  • Page 9: The Instrument

    3000 A, measuring head length 40 cm (product no. Z840C) 1 Split core current transformer MAVOWATT 210 CT-H-5A with connection cable suitable for MAVOWATT 210; 600 V CAT III; 5 A; class 0.5; cable opening diameter 10 mm (product no. Z840J) 1 Split core current transformer MAVOWATT 210 CT-H-20A with connec- tion cable suitable for MAVOWATT 210;...
  • Page 10: Instrument Overview

    MAVOWATT 210 Gossen Metrawatt GmbH Instrument Overview 5.3.1 Front Monitoring on/off Trigger limit status Power on/off Demand limit Energy direction Battery status Instrument power source Figure 2: Front Panel...
  • Page 11 Gossen Metrawatt GmbH MAVOWATT 210 5.3.2 Voltage inputs Current inputs V and I connection LEDs Figure 3: Top of instrument 5.3.3 Bottom Ground terminal DC power input Ethernet port USB port Figure 4: Bottom of instrument...
  • Page 12 MAVOWATT 210 Gossen Metrawatt GmbH 5.3.4 Icons, Buttons and Indicators Icon/Button/Indicators Description Power on/off Press to turn the instrument on. Press to turn the instrument off. Monitoring on/off Press and hold for approximately 5 seconds until a beep is heard to turn monitoring on.
  • Page 13 Gossen Metrawatt GmbH MAVOWATT 210 5.3.5 LED Indicators of Voltage (V) and Current (I) Connection LEDs V and I connection LEDs are color coded to indicate the status of channels A, B, C for voltage and current. LED Indicators of V and I Connection LEDs...
  • Page 14 MAVOWATT 210 Gossen Metrawatt GmbH 5.3.6 Measurement Cable Set, Voltage Leads Voltage leads Detachable alligator jaw safety clip Figure 5: Voltage leads 5.3.7 Flexible AC Current Probe Based on the Rogowski Principle Flexible current probe Probe output cable Probe coupling...
  • Page 15: Relevant Standards

    Gossen Metrawatt GmbH MAVOWATT 210 5.3.8 Symbols on the instrument and the included accessories: Warning concerning a point of danger (attention, observe documentation!) Double insulation (protection category II) Ground terminal European conformity marking The device may not be disposed of with household trash ...
  • Page 16: Technical Data

    MAVOWATT 210 Gossen Metrawatt GmbH EN 61000-4-6 Electromagnetic compatibility (EMC) – Part 4-6: Testing and measurement techniques – Immunity to conducted distur- bances, induced by radio-frequency fields DIN EN 60529 / Degrees of protection provided by enclosures (IP Code) IEC 60529...
  • Page 17: Characteristic Values

    Gossen Metrawatt GmbH MAVOWATT 210 Ethernet 10 Mbit/s Data Interfaces Protocols Modbus, BACnet® Internal Storage capacity 8 GB Memory Characteristic Values Sampling frequency 32 ksps (recorded and real-time meters), 128 samples per cy- cle (periodic waveform General snapshots) Sag/dip, swell trigger resolution...
  • Page 18 MAVOWATT 210 Gossen Metrawatt GmbH (True/Active) energy (P) 0.1% Reactive energy (Q) 0.1% Apparent energy (S) 0.1% Energy Fundamental active energy (P) 0.2% Parameters Fundamental reactive energy (Q) 0.2% Fundamental apparent energy (S) 0.2% Demand 0.2% Power (P) 0.2% Reactive power (Q) 0.2%...
  • Page 19: Installation

    Always set the power switch to the Off position before connecting or dis- connecting the input power cable. Note! Operation of the MAVOWATT 210 from an AC voltage source other than the rated voltage input stated on the instrument nameplate can cause damage to the instrument.
  • Page 20 MAVOWATT 210 Gossen Metrawatt GmbH During set up, the MAVOWATT 210 has to be connected directly to a com- puter (peer-to-peer connection via RJ-45 cable). It must then be configured for the network it is to be used in. After set up, the web server can be accessed from any device that is con- nected to the same network (and identical IP range) and has a web browser, e.g.
  • Page 21 Configuring the Integrated Web Server’s Network Access  The instrument is connected to a computer via wired Ethernet connection. The MAVOWATT 210 start page is displayed.  "Setting up the Connec- tion to the Integrated Web Server" 16. 1. Open Setup/Instrument Setup/Ethernet.
  • Page 22: Accessing The Integrated Web Server

    4. Open a web browser on the device (e.g. tablet or PC) that is connected to the same network. 5. Enter the IP address of the MAVOWATT 210 in the address bar of the browser. The MAVOWATT 210 information page is displayed.
  • Page 23: Integrated Web Server

    Gossen Metrawatt GmbH MAVOWATT 210 Integrated Web Server The MAVOWATT 210 has an integrated web server for configuring the instru- ment and real time data checking. During set up, you have to set up the instrument for access to your network (see ...
  • Page 24 MAVOWATT 210 Gossen Metrawatt GmbH Menu Submenu Description Model Product name Serial # Instrument serial number Version Software version OS Information OS information Survey Name Name of survey Instrument Monitoring Status Monitoring status Status Active Database File Name of active database file...
  • Page 25: Setup Page

    Gossen Metrawatt GmbH MAVOWATT 210 Setup Page 7.2.1 Survey Setup 1. Select Setup > Survey Setup to view or change the current monitoring set- tings of the instrument. Note! The survey settings can only be modified if monitoring is off. If monitoring is on, you will receive a warning that the survey settings are "view only".
  • Page 26 MAVOWATT 210 Gossen Metrawatt GmbH Menu Submenu Description Survey Name Enter a name (up to 48 characters) that de- scribes your survey. This name will be in- cluded in the name of the data file recorded. Nominal Dropdown selection: Frequency –...
  • Page 27 Gossen Metrawatt GmbH MAVOWATT 210 Nominal Nominal voltage Settable range: 90 – 600 VRMS PT Ratio Primary PT primary (if applicable) Settable range: 1 – 65535 PT Ratio PT secondary (if applicable) Secondary Settable range: 1 – 65535 Sequence Error...
  • Page 28 MAVOWATT 210 Gossen Metrawatt GmbH Nominal Nominal current for use with the current threshold settings. Settable range: 1 – 65535 IRMS Probe Type Pull down list of available flex and hinged probe types. Select the probe used or custom for probes not listed.
  • Page 29 Gossen Metrawatt GmbH MAVOWATT 210 Journal Enable Checkbox enable/disable. Journal Interval Journal interval entered in seconds. Sec. Value entered: ≥ 1 second Journal / Snapshot Snapshot Enable Checkbox enable/disable Snapshot Snapshot interval in seconds. Interval Sec. Value entered: ≥ 60 seconds Button Click to save the settings.
  • Page 30 MAVOWATT 210 Gossen Metrawatt GmbH Menu Submenu Description DHCP Checkbox enabled: An IP address will be automatically as- signed to the instrument by the network. The IP address assigned can be viewed in the Home/Instrument Status page. IP Address Instrument static IP address: Enter a valid IP address for the network being used.
  • Page 31 Discard Changes Note! The time and date of data stored in the instrument’s database is recorded in UTC time. By setting the local time zone offset, the data will appear in MAVOWATT 210 and Dran-View XP in the local time zone.
  • Page 32 MAVOWATT 210 Gossen Metrawatt GmbH 7.2.3 Downloading Configuration Downloading the instrument settings allows you to store a settings template for your surveys that can be uploaded back into the instrument for future use. 1. Select Setup > Download Config to download the instrument settings to your computer.
  • Page 33: Data Page

    Gossen Metrawatt GmbH MAVOWATT 210 Data Page 7.3.1 Real-Time Measurements Real-time measurements are updated about every 5 seconds. The table below lists the real-time parameters displayed and their units. 1. Select Data > Meters to view the real-time metering information.
  • Page 34 7.3.2 Downloading and Managing Data The List Files page allows you to download data recorded by MAVOWATT 210 to your computer for analysis using Dran-View XP, and to also delete files. 1. Select Data > List Files to view the recorded data files in the instrument’s memory.
  • Page 35 3. Click Browse to choose or create the folder where the extracted data files will be saved. 4. Click Extract to save the MAVOWATT 210 files to the location chosen. Note that MAVOWATT 210 data files are of the file type ".json".
  • Page 36: Factory Settings Page

    Each step is highlighted in green as you progress through the process. Figure 15: Firmware update 1. Select Factory > Update Firmware to update MAVOWATT 210's firmware. 2. Click the Clear button to clear previously updated firmware. 3. Click Browse to locate the firmware update file that you downloaded from the Gossen Metrawatt GmbH website.
  • Page 37 Gossen Metrawatt GmbH MAVOWATT 210 7.4.3 Restore Factory Defaults There are three options to restore MAVOWATT 210's settings to its factory defaults. 1. Select Factory. 2. Select one of the three options: – Restore Factory Default (Keep IP) Restores the factory settings but keeps the data and IP address set- tings as is (unchanged).
  • Page 38 MAVOWATT 210 Gossen Metrawatt GmbH 7.4.5 Change Password 1. Select Factory > Change Password. Figure 16: Change password 2. Enter the username and the current password in the Login field. 3. Click Login to Change Password. 4. Enter the new password in the fields New Password and Re-enter New Pass- word.
  • Page 39: Operation

    Attention! Do not exceed the marked maximum ratings. MAVOWATT 210 has three voltage and four current channels which can be used to measure a wide variety of circuit types. Refer to the appropriate con- nection diagram for the desired circuit type.  "Measurement" 38.
  • Page 40 1. Connect the alligator clips of the instrument to the circuit to be measured. 8.2.3 Connecting AC Current Probes to MAVOWATT 210  The instrument is powered off. 1. Plug the probe output cable of the current probe to the current input of the instrument.
  • Page 41: Measurement

    4. Select the applicable current probe settings in the Survey Setup of the instrument’s web server  "Survey Setup" 22. Measurement MAVOWATT 210 can monitor the following power configurations: – Single Phase – Split Phase – 3 Phase, Four Wire Wye...
  • Page 42 MAVOWATT 210 Gossen Metrawatt GmbH 8.3.1 Single Phase Measurement When making single phase measurements, use channel A as shown below. The neutral is chosen as the reference for measurement purposes. You may optionally measure the neutral current by connecting a current probe to the neutral conductor and to the N channel current input.
  • Page 43 Gossen Metrawatt GmbH MAVOWATT 210 8.3.2 Split Phase Measurement When making split phase measurements, use both channels A and C for volt- age and current connections. The neutral is chosen as the reference for mea- surement purposes. You may optionally measure the neutral current by con- necting a current probe to the neutral conductor and to the N channel current input.
  • Page 44 MAVOWATT 210 Gossen Metrawatt GmbH 8.3.3 3 Phase Measurement, Four Wire Wye Channels A, B, and C are connected to the voltage and current probes. The neutral is connected to common and is the reference for the three voltage channels. Note that the neutral current measurement is optional.
  • Page 45 Gossen Metrawatt GmbH MAVOWATT 210 8.3.4 3 Phase Measurement, 2 Probe Delta The figure below shows the 3 phase, 2 probe, 2 wattmeter delta connection using phase channels A-B-C. The N channel is connected to phase B as the reference for measurement pur- poses.
  • Page 46 MAVOWATT 210 Gossen Metrawatt GmbH 8.3.5 3 Phase Measurement, 3 Probe Delta The figure below shows the 3 phase, 3 probe, 2 wattmeter delta connection using phase channels A-B-C. The N channel is chosen as the reference and is connected to phase B for measurement purposes.
  • Page 47: Start Monitoring

    Gossen Metrawatt GmbH MAVOWATT 210 Start Monitoring Monitoring can be started by using either the instrument’s keypad or via the integrated web server. 8.4.1 Starting Monitoring via Instrument Keypad  The measurement connections have been made.  The instrument is powered on.
  • Page 48: Stop Monitoring

    In order to view and analyze data recorded by MAVOWATT 210 with Dran-View XP software, you must first copy the MAVOWATT 210 data files to your com- puter. MAVOWATT 210 data files are stored in a json (JavaScript Object Nota- tion) file format and have a ".json"...
  • Page 49  Dran-View XP is installed on your computer. 8.7.2 Download Data Files from MAVOWATT 210 to a Computer via Web Server 1. Download data to a computer via the integrated web server  "Download- ing and Managing Data" 31.
  • Page 50 MAVOWATT 210 Gossen Metrawatt GmbH  The data recorded by MAVOWATT 210 is displayed. Figure 24: Displaying data in Dran-View XP For a detailed description of Dran-View XP features, refer to the software docu- mentation available after installation of Dran-View XP.
  • Page 51: Maintenance

    Gossen Metrawatt GmbH MAVOWATT 210 Maintenance Cleaning Attention! Do not immerse. Clean the instrument by wiping it gently with a damp, lint-free cloth. A mild detergent can be used if desired. Maintenance To ensure the accuracy of the instrument, the instrument must be calibrated at least once every 12 months.
  • Page 52: Calibration

    MAVOWATT 210 Gossen Metrawatt GmbH Calibration Using your device and the stressing it is subjected to in doing so may result in deviation from the specified levels of accuracy. In the case of strict measuring accuracy requirements, as well as frequent stress (such as considerable climatic or mechanical stressing), we recommend a relatively short calibration interval of once per year.
  • Page 53: 10 Contact, Support And Service

    Gossen Metrawatt GmbH MAVOWATT 210 10 Contact, Support and Service You can reach Gossen Metrawatt GmbH directly and uncomplicated, we have one number for everything! Whether it’s a support question, or individual desire, we answer every request Monday–Thursday: 8:00 a.m. – 4:00 p.m.
  • Page 54: 11 Ce Declaration

    MAVOWATT 210 Gossen Metrawatt GmbH 11 CE Declaration The instrument fulfills all requirements of applicable EU directives and national regulations. We confirm this with the CE mark. The CE Declaration of Confor- mity is available upon request. 12 Returns and Environmentally Sound Disposal...
  • Page 55 Gossen Metrawatt GmbH MAVOWATT 210...
  • Page 56 MAVOWATT 210 Gossen Metrawatt GmbH © Gossen Metrawatt GmbH Prepared in Germany • Subject to change, errors excepted • PDF version available on the Internet All trademarks, registered trademarks, logos, product names, and company names are the property of their respective owners.

Table of Contents