7. The recommended torque setting for terminals is shown as below.
I/P: 3.4 kgf-cm (3.0 Lb-in).
O/P: 5 kgf-cm (4.4 Lb-in).
8. Suggested fuse and maximum number of the power supply units that can be connected
to a circuit breaker at 230 V are shown as below.
Fuse: T3.15A/H250V.
Circuit breaker: C16 - 7, D16 - 14.
9. DIN rail mounting:
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not
be possible. Admissible DIN rail: TS35/7.5 or TS35/15.
A. Tilt the unit slightly rearwards.
B. Fit the unit over top hat rail.
C. Slide it downward until it hits the stop.
D. Press against the bottom for locking.
E. Shake the unit slightly to check the locking action.
Connecting the Power Supply to a Switch
Connect the wires from the power supply to a compatible switch by inserting the positive
and negative wires into the corresponding contacts. Tighten the wire-clamp screws to
prevent the wires from being loosened.