Replacement Of Expansion Valve - Hitachi SAMURAI Series Service Manual

Water cooled water chillers -modular-r134a-screw type
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

3 Servicing
Cycle components

3.3.6 Replacement of expansion Valve

1 Collect the refrigerant as explained in section
"3.3.3 Recovering the refrigerant"
2 Firmly hold the coil of the expansion valve
and pull out upward. It is easier to remove the
expansion valve coil if it is rotated while pulling
it up.
3 Remove the brazed parts using a blowtorch
and previously cooling the pipe side with wet
cloth in order to avoid brazing material entering
the pipe circuit.
Pay attention to the following points when replacing an expansion valve.
a. This unit uses an electronic expansion valve, which is normally closed when the compressor stops. For this
reason, when the valve upstream of the expansion valve (liquid outlet valve of the heat exchanger) is closed,
refrigerant may accumulate between the liquid outlet valve of the heat exchanger and the expansion valve. In
case of removing the brazed part of the expansion valve, always conduct this work after selecting expansion valve
manual output function at the service menu in order to force the opening of the expansion valve, and release both
the primary and the secondary side.
b. After replacement of the expansion valve, the value managed by the control and the actual opening do not match.
In order to fix this, always conduct a zero point adjustment (power reactivation).
70
SMGB0120 rev.0 - 11/2017
Expansion
valve coil
Expansion
valve
Brazed
parts

Advertisement

Table of Contents
loading

Table of Contents