Blower data

Airflow performance data is based on cooling performance with a coil and no filter in place. Check
the performance table for appropriate unit size selection. External static pressure should stay within
the minimum and maximum limits shown in the table below to ensure proper cooling, heating, and
electric heating operation.
NOTES:
• Required 350-450 CFM/Ton range.
• When there is an electric heater, set the fan speed based on the air volume that the electric
heater needs (not less than 350 CFM/Ton).
• Airflow based upon air handler unit operates at 230 V with no electric heater kit and no filter.
Airflow at 208 V is approximately the same as 230 V.
¢ Model: WHM24DMA21S
Fan speed
Tap (2)
Default setting
Tap (3)
Tap (4)
Tap (5)
¢ Model: WHM36DMA21S
Fan speed
Tap (2)
Default setting
Tap (3)
Tap (4)
Tap (5)
0
0.1
(0)
(0.02)
CFM
815
792
W
94
102
CFM
862
828
W
106
114
CFM
W
CFM
W
0
0.1
(0)
(0.02)
CFM
1,264
1,216
W
215
222
CFM
1,350
1,314
W
257
264
CFM
W
CFM
W
External static pressure
in.H2O [KPa]
0.18
0.3
0.4
(0.045)
(0.07)
(0.1)
752
709
110
123
792
735
705
125
137
145
859
853
178
185
External static pressure
in.H2O [KPa]
0.18
0.3
0.4
(0.045)
(0.07)
(0.1)
1,172
1,135
1,096
233
238
244
1,269
1,206
1,116
274
282
292
1,323
1,266
304
313
1,350
371
- 19 -
0.5
0.6
0.7
(0.12)
(0.15)
(0.17)
803
769
735
193
203
213
895
864
825
241
251
258
0.5
0.6
0.7
(0.12)
(0.15)
(0.17)
1,082
1,050
297
302
1,192
1,122
1,060
323
333
340
1,292
1,221
1,148
381
394
401
0.8
(0.20)
779
267
0.8
(0.20)
1,088
406