Overview > Unit
Control Variables
User can set the following 3 control points of DOAS Unit.
① Unit ON/OFF: User can adjust "Enabled/Disabled" of DOAS Unit.
② Occupancy: User can adjust occupancy manually "Occupied / Unoccupied."
③ Temperature Setpoint: User can adjust temperature setpoint.
Monitoring
Displays the DOAS Unit's information
- Operation Status (Cooling / Dehumidifying / Heating / Fan only / Defrosting)
- Outside Air Condition (DB / RH)
- Outdoor Unit information (High & Low pressure / Comp Hz / Fan Speed)
- Multi V interlocking energy saving function status.
- Double Energy Recovery system status
④ Trend Saving
Service manager can save the control variables and monitoring points.
[Click Icon (④) > Set file Name > Click "Start" > Click "Stop" > file save as CSV file at "Download folder"]
Displays the Unit's overview.
User can adjust Unit Enable, Occupancy and Target Temperature Setpoint.
(Service Manager and Manufacturer accounts only)