Co Interlock; Advanced - LG ARND153DCR4 Manual

Hide thumbs Also See for ARND153DCR4:
Table of Contents

Advertisement

CO
INTERLOCK
2

ADVANCED

The CO
Interlock menu allows the user to enable the CO
2
control parameters which related with Fan operation
CO
INTERLOCK ENABLE
2
This screen allows the user to Enable the CO
CO
INTERLOCK SETTINGS
2
This screen allows the user to adjust CO
- Setpoint: Target Space CO
- Stop Setpoint: Fan stop when Space CO
- Hysteresis: The fan speed is adjusted by reflecting the hysteresis in the target
value
The Advanced menu allows the user to access several submenus regarding
controller information, and unit configuration. Submenu options are read only and will
require the user to input proper login criteria. The service password (7600) is
required to change service access menus. Consult factory for factory level access.
The Unit Configuration Settings Menus allows the user to view and adjust Altitude
and functions
ALTITUDE
This screen allow to adjust the Altitude. The unit altitude is used for the enthalpy
calculation.
FUNTIONS SETTINGS
This screen allow to set functions.
-. Power Loss Auto Reset:
-. Shut Down Alarm Auto Reset:
-. Forced
Operation:
Interlock function
2
interlock mode control parameter
2
(ppm)
2
value is below Stop Setpoint
2
interlock mode and adjust
2
21